WEEKLY UNIT ACTIVATION
In accordance with ANSI Z358.1 or AS 4775
(whichever is applicable).
The unit should be activated every week for a period
long enough to verify operation and ensure the flushing
fluid is available. The tank must then be refilled to the
correct height.
Note: the intent is to ensure that there is a flushing fluid
supply at the head of the device and to clear the supply
line of any sediment build up that could prevent fluid
from being delivered to the head of the device and to
minimise microbial contamination due to sitting water.
Internal eye wash strainer should also be removed and
cleaned during this process or when required.
ANNUAL INSPECTION
In accordance with ANSI Z358.1 or AS4775
(whichever is applicable).
Shower units and eye wash shall be inspected annually
by a qualified technician to ensure ongoing performance.
INSPECTION TAGS
Inspection tags are available (if not already supplied) to
record weekly and annual inspections. If you need to
purchase inspection tags contact Enware.
FILTER MAINTENANCE
Filters to be checked and cleaned once a month or in
accordance with usage. Filters are located at Y-Strainer
on the inlet fill assembly, and at the filter strainer in the
eye wash tee piece.
WATER QUALITY CHECK
Enware recommends that water quality is checked for
suitability of use in an emergency. These checks should
be done periodically (at intervals based on the specific
site risk assessment) to determine if the flushing fluid
needs to be replaced.
CLEANING THE TANK
It is recommended to empty the tank periodically to
ensure good water quality. The interval will depend on
the specific site risk assessment.