enware ET1400F Скачать руководство пользователя страница 6

Call 1300 369 273 

www.enware.com.au

8.  Locate the inlet fill assembly and fit to the Inlet connection of 

the tank

 (SEE IMAGE 13).

 

 

The union connection will have to be disassembled to screw 

the top elbow in. Use appropriate thread sealing tape, to seal 

the inlet connection.  

 

NOTE:

 

Inlet connection for inlet fill assembly is noted by an arrow 

directed into tank. 

 

Overflow outlet is noted by an arrow out of tank. 

 

 

Assemble union connections for inlet fill assembly, then 

secure the inlet fill assembly onto tank frame using brackets 

supplied. The frame has pre-drilled holes to accomodate 

the 2x bracket fixing screws (M6 head cap screws). Place 

rubber clamps around the plastic pipe to secure the inlet fill 

assembly onto bracket. 

 

 

 

 

 

 

9.  Reach inside bottom access of tank, and pull the activation 

valve arm down. Use appropriate step ladder to do so. 

 

Attach shower activation pull handle to the activation valve 

arm using the nut and bolt supplied 

(SEE IMAGE 14).

 

 

 

INSTALLATION IS NOW COMPLETED AND THE TANK SHOWER IS 

READY TO BE COMMISSIONED.

 

 

SEE PAGE 6 FOR COMMISSIONING.

IMAGE 13

IMAGE 14

Содержание ET1400F

Страница 1: ...ce wash equipment shall be in accordance with AS4775 or ANSI Standard Z358 1 whichever is applicable to the installation Tank Shower frame is not Cyclone Rated when mounted on FRP Grid Base Tank Showe...

Страница 2: ...frame that comes in 6 parts and will need to be assembled on site before commencing SEE IMAGE 2 The Flat Pack frame is located inside the tank for transportation ready to be lifted out of the tank vi...

Страница 3: ...upplied as shown with four FRP Grating Mats and five Clamping Plate Sets SEE IMAGE 3 IMAGE 4 2 Position the Grating Mats as shown taking note of the orientation of the pre installed Mounting Plates SE...

Страница 4: ...securely to the ground For installation requiring cyclone wind category rating see page 7 Important Ensure the frame is installed on a flat level surface INSTALLING ONTO GROUND WITH RELOCATABLE FOOT...

Страница 5: ...Y to be lifted when completely empty of water 6 Use 80mm bolts x10 and two larger washers Acetyl and stainless steel supplied for each bolt to fix the tank in place Acetyl plastic washer should be pla...

Страница 6: ...or inlet fill assembly then secure the inlet fill assembly onto tank frame using brackets supplied The frame has pre drilled holes to accomodate the 2x bracket fixing screws M6 head cap screws Place r...

Страница 7: ...0mm max GP 32 REINFORCED CONCRETE FOOTING SPECIFICATIONS Reinforced concrete footing is to be a minimum 2000 x 2000 x 200mm SEE FIGURE 2 with 16mm Diameter Bars with a Tensile Stress Capacity of 500 M...

Страница 8: ...n activating the eye wash for the first time take the aerators out of eye wash outlet to clear the line of any debris Check for any leaks in joints and connections 4 Turn shower and eye wash off and c...

Страница 9: ...CK FRAME TO PALLET ET14SP002 10 X BOLTS M16X80 10 X ACETAL WASHERS 10 X SS316 WASHERS M16 WATER LEVEL ASSEMBLY ET14SP003 TEMPERATURE GAUGE ET14SP004 SIGNAGE SHOWER EYEWASH STAINLESS STEEL ET14SP005 FL...

Страница 10: ...ULL HANDLE ASSEMBLY ET14SP008 EYEWASH CONNECTOR KIT ET14SP009 EYEWASH OUTLET KIT ET14SP010 ASSEMBLED FOOT BASE CLAMP KIT ET14SP011 ASSEMBLED FOOT BASE CENTRE CLAMP KIT ET14SP012 ASSEMBLED FOOT BASE CL...

Страница 11: ...r Do not use cleaning agents containing a corrosive acid sourcing agent or solvent chemicals Do not use cream cleaners as they are abrasive Damage caused this way will not be covered by warranty Descr...

Страница 12: ...sure ongoing performance INSPECTION TAGS Inspection tags are available if not already supplied to record weekly and annual inspections If you need to purchase inspection tags contact Enware FILTER MAI...

Отзывы: