5
Call 1300 369 273
www.enware.com.au
5. Check that the tank is not filled with water before installing
tank to the frame.
Lift the tank onto the frame using a forklift or a crane. When
lifting using a sling, use the four lifting lugs located on the top
corners of the tank.
Take care to align the bolt mounting holes on the frame
with the matching threaded holes on the bottom of the tank
assembly
(SEE IMAGE 10).
Tank is ONLY to be lifted when completely empty of water.
6. Use 80mm bolts (x10) and two larger washers (Acetyl and
stainless steel supplied) for each bolt, to fix the tank in place.
Acetyl (plastic) washer should be placed closest to the frame,
so that the Acetyl washer is sandwiched between the frame
and stainless steel washer
(SEE IMAGE 11).
Apply Anti-Seize onto bolt thread before tightening.
Tighten bolts firmly but do not over-tighten.
7. Insert the eyewash hose into the bulk head fitting, and push
until it bottoms out
(SEE IMAGE 12).
(The fitting is a push-fit
connector and does not require further tightening.)
IMAGE 10
IMAGE 11
IMAGE 12