29
NXW REVERSIBLE CHILLER INSTALLATION MANUAL
Operating Parameters
Compressor Resistance
Model
208-230
460
575
096
0.610
2.330
4.060
108
0.610
2.330
4.060
120
0.562
2.270
3.560
140
0.422
2.200
3.289
180
0.320
1.298
1.999
210
0.320
1.298
1.999
240
0.330
1.110
1.710
360
0.226
0.833
1.268
540
n/a
0.450
0.701
1/15/10
Heating Mode
Entering
Load Temp (°F)
Entering
Source Temp (°F)
Suction
Pressure (psig)
Discharge
Pressure (psig)
Superheat
(°F)
Subcooling
(°F)
60
30
75-100
200-215
10-12
10-13
50
100-125
200-215
12-14
8-12
70
125-150
215-230
14-18
8-12
90
150-165
230-255
25-30
8-12
80
30
75-100
285-300
10-12
10-13
50
100-125
300-315
12-14
8-12
70
125-150
315-330
14-18
8-12
90
150-165
330-345
25-30
8-12
100
30
85-110
365-380
10-12
7-11
50
110-135
385-400
12-14
7-11
70
135-165
400-415
14-18
3-7
120
50
110-135
485-500
12-14
7-11
70
135-165
500-515
14-18
3-7
1/15/10
Cooling Mode
Entering
Load Temp (°F)
Entering
Source Temp (°F)
Suction
Pressure (psig)
Discharge
Pressure (psig)
Superheat
(°F)
Subcooling
(°F)
50
30
80-90
140-175
15-20
3-6
50
90-100
200-235
11-15
6-9
70
100-110
250-285
11-15
9-12
90
100-120
330-365
8-12
12-14
110
110-130
430-465
8-12
14-19
70
30
80-90
150-185
15-20
3-6
50
90-100
210-245
11-15
6-9
70
100-110
260-295
11-15
9-12
90
110-120
340-375
8-12
12-14
110
110-140
440-485
8-12
14-19
90
30
80-90
150-185
15-20
3-6
50
90-100
210-245
11-15
6-9
70
100-110
260-295
11-15
9-12
90
110-120
340-375
8-12
12-14
110
30
90-100
160-195
40-45
3-6
50
110-130
220-255
30-40
6-9
1/15/10
NOTE:
Operating data based on normal conditions with 3 gpm/ton for the load and source.
NOTE:
Operating data based on normal conditions with 3 gpm/ton for the load and source.