NXW REVERSIBLE CHILLER INSTALLATION MANUAL
Menu and Menu Contents
Alarm
Displays unit alarms until the unit has been reset (Unit
•
alarms can be reset by holding both the Escape (ESC)
key and Return (
←
) key for five seconds or by power
cycling the unit.)
Alarm History
If a fault occurs the fault will be recorded in history
viewable on the unit mounted display. Each fault type will
be displayed in the history menu with a number between 0
and 3. A reading of 3+ means that the fault has occurred
more than 3 times in the past. The history menu can be
cleared with a power cycle only. Alarm date and time are
not included in the history.
Unit Alarms
Unit alarms are shown on the display once the unit has
locked out.
Load Flow – Load flow switch is not closed
The load flow switch must be closed prior to either
•
compressor starting and must remain closed for the
entire run time of the compressor(s).
Low Pressure 1 – Compressor Circuit 1 Low Pressure
switch
The low pressure switch is checked before compressor
•
start up and is monitored during compressor operation.
Src FP 1 Temp Low – Source Freeze Detection
Sensor 1
The source freeze detection sensor on compressor circuit
•
1 has reached its setpoint.
Src FP 1 Sensor Bad
The sensor for Source freeze detection on compressor
•
circuit 1 is unreliable or is not reading.
LD FP 1 Temp Low – Load Freeze Detection Sensor 1
The load freeze detection sensor on compressor circuit 1
•
has reached its setpoint.
LD FP 1 Sensor Bad
The sensor for Load freeze detection on compressor
•
circuit 1 is unreliable or is not reading.
Source Flow – Source Flow switch is not closed
The source flow switch must be closed prior to either
•
compressor starting and must remain closed for the
entire run-time of the compressor(s).
Unit Display and Interface cont.
High Pressure 1 – Compressor Circuit 1 High Pressure
Switch
If high pressure switch 1 opens at any time during
•
compressor 1 run time the compressor will be shut down
immediately.
Low Pressure 2 - Compressor Circuit 2 Low Pressure
Switch
The low pressure switch is checked before compressor
•
start up and is monitored during compressor operation.
Src FP 2 Temp Low - Source Freeze Detection
Sensor 2
The source freeze detection sensor on compressor circuit
•
2 has reached its setpoint.
Src FP 2 Sensor Bad
The sensor for Source freeze detection on compressor
•
circuit 2 is unreliable or is not reading.
LD FP 2 Temp Low - Load Freeze Detection Sensor 2
The load freeze detection sensor on compressor circuit 2
•
has reached its setpoint.
LD FP 2 Sensor Bad
The sensor for Load freeze detection on compressor
•
circuit 2 is unreliable or is not reading.
High Pressure 2 - Compressor Circuit 2 High
Pressure Switch
If high pressure switch 2 opens at any time during
•
compressor 2 run time the compressor will be shut down
immediately.
Comp Start Failure – Compressor Start Failure
If either compressor fails to start when the contactor
•
pulls in the compressor current switch will cause that
compressor to be locked out after 2 retries. The other
compressor will continue to operate normally in this
condition.