24
NXW REVERSIBLE CHILLER INSTALLATION MANUAL
DUAL STAGE WW
Input Name
Input
Output Name
Output
Entering Load Water Temperature
AI 1
Compressor 1
DO1
Leaving Load Water Temperature 1
AI 2
Compressor 2
DO2
Source Heating Freeze Detection 1
AI 3
Reversing Valve
DO3
Source Heating Freeze Detection 2
AI 4
Accessory
DO4
Load Cooling Freeze Detection 1
AI 5
Compressor 1 Alarm
DO5
Load Cooling Freeze Detection 2
AI 6
Compressor 2 Alarm
DO6
Network Output
DO7
Load Flow Proving Switch
DI 1
Network Output
DO8
Emergency Shutdown
DI 2
Network Output
D09
Stage 2 Low Pressure
DI 3
Source Htg Freeze Detection Select - 30ºF DI 4
Future
PWM1
Load Htg Freeze Detection Select - 30ºF
DI 5
Future
PWM2
Stage 1 Low Pressure
DI 6
Thermostat Y1
DI 7
Thermostat Y2
DI 8
Thermostat B
DI 9
Source Flow Proving Switch
D10
Stage 1 High Pressure
DI11
Stage 2 High Pressure
DI12
XP10 Expansion Card
Input Name
Input
Output Name
Output
Entering Source Water Temperature
AI 1
Unused
DO 1
Leaving Source Water Temperature 1
AI 2
Unused
DO 2
Current Switch 1 - Compressor 1
AI 3
Unused
DO 3
Current Switch 2 - Compressor 2
AI 4
Unused
DO 4
Inputs and Outputs Configuration
The Johnson FX10 Board is specifically designed for
commercial heat pumps and provides control of the entire
unit as well as input ports for Open N2, Lontalk and BACnet
communications protocols as well as an input port for a user
interface.
Networking Protocol