14
NXW REVERSIBLE CHILLER INSTALLATION MANUAL
Electrical Data
HACR circuit breaker in USA only.
* - MCC, RLA, & LRA rating per compressor. Breaker and FLA sized for both compressors.
Model
Rated
Voltage
Voltage
Min/Max
Compressor*
Total
Unit FLA
Min
Circ Amp
Max
Fuse/HACR
MCC
RLA
LRA
096
208-230/60/3
187/253
24.9
15.9
110.0
31.9
36.0
50
460/60/3
414/506
12.1
7.7
52.0
15.4
17.3
25
575/60/3
517/633
8.9
5.7
38.9
11.4
12.8
15
108
208-230/60/3
187/253
28.0
17.3
120.0
34.6
38.9
50
460/60/3
414/506
15.0
9.6
70.0
19.2
21.6
30
575/60/3
517/633
12.5
8.0
53.0
16.0
18.0
25
380/60/3
342/418
14.1
9.0
94.0
18.0
20.3
25
120
208-230/60/3
187/253
35.0
22.4
149.0
44.8
50.4
70
460/60/3
414/506
16.5
10.6
75.0
21.2
23.9
30
575/60/3
517/633
12.0
7.7
54.0
15.4
17.3
25
380/60/3
342/418
17.1
11.0
88.0
22.0
24.8
35
140
208-230/60/3
187/253
35.0
22.4
190.0
44.8
50.4
70
460/60/3
414/506
19.0
12.2
87.0
24.4
27.5
35
575/60/3
517/633
15.0
9.6
62.0
19.2
21.6
30
380/60/3
342/418
19.0
12.2
73.0
24.4
27.5
35
180
208-230/60/3
187/253
45.0
26.6
235.0
53.2
59.9
80
460/60/3
414/506
19.0
12.2
110.0
24.4
27.5
35
575/60/3
517/633
16.5
10.9
95.0
21.8
24.5
35
380/60/3
342/418
26.0
16.7
123.0
33.4
37.6
50
210
208-230/60/3
187/253
47.0
31.0
235.0
62.0
69.8
100
460/60/3
414/506
25.0
16.0
110.0
32.0
36.0
50
575/60/3
517/633
17.3
11.9
95.0
23.8
26.8
35
380/60/3
342/418
30.0
19.2
140.0
38.4
43.2
60
240
208-230/60/3
187/253
52.2
35.2
250.0
70.4
79.2
110
460/60/3
414/506
27.0
19.2
140.0
38.4
43.2
60
575/60/3
517/633
19.1
14.5
100.0
29.0
32.6
45
380/60/3
342/418
37.0
23.7
145.0
47.4
53.3
70
360
208-230/60/3
187/253
87.0
55.8
340.0
111.5
125.5
175
460/60/3
414/506
42.0
26.9
173.0
53.8
60.6
80
575/60/3
517/633
37.0
23.7
132.0
47.4
53.4
70
380/60/3
342/418
53.0
34.0
196.0
67.9
76.4
100
540
460/60/3
414/506
67.0
42.9
250.0
85.8
96.5
125
575/60/3
517/633
50.0
32.0
198.0
64.0
72.0
100
380/60/3
342/418
85.0
54.4
305.0
108.8
122.4
175
3/9/09