Installation Instructions

AFTER INSTALLING THIS UNIT,

PLEASE PASS ONTO END USER

DO NOT THROW AWAY

Ducting Connections
Read and observe the Safety section

The energiSava

®

 500 unit has a label with the 

icons indicating which port is which.

It is very important that ducting is connected 

to the correct ports in line with the icons below.

Condensate Drain

The unit’s condensation drain pipe must be 

fitted and connected to the dwelling’s foul water 

drainage system in accordance with the relevant 

building regulations.

The Condensate Drain Pipe:

• Is attached via the condensation drain socket 

on the base of the unit.

• Must incorporate a suitable trap, which must 

act as an air lock, ie must be sealed.

• Should be installed to have a minimum 5° fall 

from the unit.

• Must be adequately secured and be insulated 

with the equivalent of at least 25mm of 

insulating material with a thermal conductivity 

of 0.04 W/(mK) if any part of the pipe passes 

though an unheated void.

• EnviroVent recommend the use of diaphragm 

type waste valve in place of a conventional 

‘wet’ trap which could dry out.

Fitting

1.  Fit hose clamp around the condensate drain 

socket, ensuring it is pushed over the lip and 

aligned with a screwdriver access hole to 

enable tightening of the hose clamp.

2.  Insert 22mm O/D PVC pipe into condensate 

drain socket up to the stop, no more than 

50mm of pipe should be inserted into the 

condensate drain socket.

3.  Hand tighten the hose clip. Do not over tighten.

 

 

EXTRACT FROM DWELLING

 

This duct port is connected to the ducting that 

carries waste air from the ‘Wet Rooms’ to the unit. 

TO ATMOSPHERE 

This duct port is connected to the ducting that 

carries the waste air to outdoors from the unit.

 

SUPPLY TO DWELLING

This duct port is connected to the ducting that 

carries the fresh warmed air to the habitable 

rooms from the unit.

FROM ATMOSPHERE

This duct port is connected to the ducting that 

carries fresh outdoor air to the unit.

Wiring Connections Access

All wiring must conform to current I.E.E. 

Wiring Regulations and all applicable national 

standards and Building Regulations.

Read and observe the Safety section.

The electronics compartment is mounted on top 

of the unit. The compartment has two removable 

lids, front & rear. The front lid must always be 

removed before the rear lid; both lids are fixed by 

four screws. All wiring must be routed into the 

electronics compartment via the knock-outs and 

using cable glands or similar fitted to the rear lid.

Non-return valve

WALL SIDE

Содержание energiSava 500

Страница 1: ...energiSava 500 INSTALLATION GUIDE FOR ENGINEER INSTALLER...

Страница 2: ...24AWG Stranded Tinned Copper 11 Control communication cables should not be placed within 50mm or on the same metal cable tray as any 230V lighting or power cables 12 Ensure all cable glands are fully...

Страница 3: ...f should be insulated or a condensate trap should be fitted just below roof level 5 Ducts within the building heated envelope between the external terminals and the unit sFromAtmosphereandToAtmosphere...

Страница 4: ...Auto Setback Speed 7 Continuous Speed 7 Boost Speed with Overrun Timer 7 Status Indicator Boost Alert 8 Summer Bypass 8 Summer Kick Up Mode 8 Automatic Frost Protection 8 Integrated Humidity Sensor 8...

Страница 5: ...efore being ducted to the outside Fresh air is drawn into the unit from outside which is warmed by the heat exchange cell and delivered into the living dining and bedroom areas Packaging Contents Insp...

Страница 6: ...difficult for maintenance and repair The unit MUST be mounted level front to back and side to side 1 Mark a horizontal line on the wall using a spirit level This line will be approximately 330mm below...

Страница 7: ...nsuring it is pushed over the lip and aligned with a screwdriver access hole to enable tightening of the hose clamp 2 Insert 22mm O D PVC pipe into condensate drain socket up to the stop no more than...

Страница 8: ...t speed increases the extract and supply air flow Boost speed is configured with step less independent fan controls and includes an overrun timer variable between 0 and 60 minutes The boost speed can...

Страница 9: ...ink wire will enable summer kick up mode When summer kick up mode is trigged by summer bypass the increased fan speed can be prevented either manually or automatically Manual This is by means of a vol...

Страница 10: ...and Controls Status Indicator Mains cable must be separate from the communication cables See Important Information Supply wiring diagram 230V Connection at indicator Connection at unit L N 12V A B 0V...

Страница 11: ...HR There is maximum of 10 single pole switches or humidistats that can be used To Boost using switch live a relay is required SWHT BOXRELAY Momentary Boost switch SWHT BOOST M Volt free setback switch...

Страница 12: ...inuous speed and boost speed are programmed by placing the controller into program mode via the program run switch and changing the position of the rotary potentiometers When applying power for the fi...

Страница 13: ...n program run switch to centre position to exit commissioning For the commissioning settings to be stored the unit needs to be powered up Continuous Supply Extract Speeds Move program run switch to co...

Страница 14: ...from the run position to the continuous position from the continuous position to the boost position and back to the run position To ensure that the reset switch movements are registered by the control...

Страница 15: ...or best results 1 Slide out filters fitted either side of heat exchanger 2 Carefully remove any dust from face of heat exchanger interior of the unit and the bypass using a vacuum cleaner Do not use w...

Страница 16: ...tion press hold the reset switch with a ball point pen or similar object for 10 seconds The switch is located behind the small hole in the front of the status indicator All lights will momentarily be...

Страница 17: ...out charges may apply if a fault cannot be identified Supply Only If your product has been supplied by EnviroVent and installed by a third party it is covered by a two year parts only warranty If you...

Страница 18: ...17 energiSava 500 SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL US ON 0345 27 27 810 Serviced By Company Date Notes Service Record...

Страница 19: ...it or the package indicates that disposal of this unit after its lifecycle could harm the environment Do not dispose the unit as unsorted municipal waste it should be disposed by a specialized company...

Страница 20: ...read carefully to ensure simple installation and a long trouble free life for the user Delivering innovative and sustainable ventilation solutions worldwide EnviroVent Ltd EnviroVent House Hornbeam B...

Отзывы: