Maintenance

Filter Replacement

Filters should be replaced at least annually, or more regularly dependent on environmental 

conditions. The status indicator will indicate filter change required in line with the filter change 

interval setting. Replacement filters are available from EnviroVent.

G4 Filter Set

2 framed filters

FILTER-G4-ES500

Status Indicator Filter Notification Reset

Ensure the unit is powered up. To clear the 

status indicator filter notification press & 

hold the reset switch with a ball point pen 

or similar object for 10 seconds. The switch 

is located behind the small hole in the 

front of the status indicator. All lights will 

momentarily be illuminated indicating a 

successful reset.

1.  Remove front cover, see page14.  
2.  Slide out filters fitted either side of heat 

exchanger as shown.

3.  Replace filters by carefully sliding the 

replacement filters either side of the heat 

exchanger.

4.  Ensure arrows printed on the ends of the 

Filters point towards the heat exchanger.  

Units use unequal length filters. When 

replacing filters ensure the short filter is 

fitted to the right hand side of the heat 

exchanger, see illustration.

5.  Replace the front cover. When refitting 

front cover do not overtighten screws.

Содержание energiSava 500

Страница 1: ...energiSava 500 INSTALLATION GUIDE FOR ENGINEER INSTALLER...

Страница 2: ...24AWG Stranded Tinned Copper 11 Control communication cables should not be placed within 50mm or on the same metal cable tray as any 230V lighting or power cables 12 Ensure all cable glands are fully...

Страница 3: ...f should be insulated or a condensate trap should be fitted just below roof level 5 Ducts within the building heated envelope between the external terminals and the unit sFromAtmosphereandToAtmosphere...

Страница 4: ...Auto Setback Speed 7 Continuous Speed 7 Boost Speed with Overrun Timer 7 Status Indicator Boost Alert 8 Summer Bypass 8 Summer Kick Up Mode 8 Automatic Frost Protection 8 Integrated Humidity Sensor 8...

Страница 5: ...efore being ducted to the outside Fresh air is drawn into the unit from outside which is warmed by the heat exchange cell and delivered into the living dining and bedroom areas Packaging Contents Insp...

Страница 6: ...difficult for maintenance and repair The unit MUST be mounted level front to back and side to side 1 Mark a horizontal line on the wall using a spirit level This line will be approximately 330mm below...

Страница 7: ...nsuring it is pushed over the lip and aligned with a screwdriver access hole to enable tightening of the hose clamp 2 Insert 22mm O D PVC pipe into condensate drain socket up to the stop no more than...

Страница 8: ...t speed increases the extract and supply air flow Boost speed is configured with step less independent fan controls and includes an overrun timer variable between 0 and 60 minutes The boost speed can...

Страница 9: ...ink wire will enable summer kick up mode When summer kick up mode is trigged by summer bypass the increased fan speed can be prevented either manually or automatically Manual This is by means of a vol...

Страница 10: ...and Controls Status Indicator Mains cable must be separate from the communication cables See Important Information Supply wiring diagram 230V Connection at indicator Connection at unit L N 12V A B 0V...

Страница 11: ...HR There is maximum of 10 single pole switches or humidistats that can be used To Boost using switch live a relay is required SWHT BOXRELAY Momentary Boost switch SWHT BOOST M Volt free setback switch...

Страница 12: ...inuous speed and boost speed are programmed by placing the controller into program mode via the program run switch and changing the position of the rotary potentiometers When applying power for the fi...

Страница 13: ...n program run switch to centre position to exit commissioning For the commissioning settings to be stored the unit needs to be powered up Continuous Supply Extract Speeds Move program run switch to co...

Страница 14: ...from the run position to the continuous position from the continuous position to the boost position and back to the run position To ensure that the reset switch movements are registered by the control...

Страница 15: ...or best results 1 Slide out filters fitted either side of heat exchanger 2 Carefully remove any dust from face of heat exchanger interior of the unit and the bypass using a vacuum cleaner Do not use w...

Страница 16: ...tion press hold the reset switch with a ball point pen or similar object for 10 seconds The switch is located behind the small hole in the front of the status indicator All lights will momentarily be...

Страница 17: ...out charges may apply if a fault cannot be identified Supply Only If your product has been supplied by EnviroVent and installed by a third party it is covered by a two year parts only warranty If you...

Страница 18: ...17 energiSava 500 SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL US ON 0345 27 27 810 Serviced By Company Date Notes Service Record...

Страница 19: ...it or the package indicates that disposal of this unit after its lifecycle could harm the environment Do not dispose the unit as unsorted municipal waste it should be disposed by a specialized company...

Страница 20: ...read carefully to ensure simple installation and a long trouble free life for the user Delivering innovative and sustainable ventilation solutions worldwide EnviroVent Ltd EnviroVent House Hornbeam B...

Отзывы: