FAN MOUNT (TYPICAL MOUNTING TYPES),
continued
TRUSS MOUNT INSTALLATION
NOTE:
The recommended additional structural material for truss
mounting is 1-5/8" x 1-5/8" strut channel beams and hardware.
Other structural materials may be used but consult factory
prior to use.
1.
Size the strut channel beams to ensure at least 3" of
overlap at each end on adjoining building truss members.
2. Locate the mount bracket at the desired location (center
preferred) on the strut channel beams and fasten using
the provided 6017873 and 6015118 3/8" dia. grade 5
hardware. Use 6017852 clamp plates as required. Torque
to 20-28 ft-lbs.
3. Locate beam/mount assembly on building truss system.
See Fig. 5. (top mounting preferred)
4. Fasten strut channel beams to building truss system using
3.8" dia., grade 5 hardware (not provided).
DO NOT
use
spring loaded strut channel beam hardware. Locking
hardware (nuts and washers) required.
Z-PURLIN MOUNT INSTALLATION – (OPTIONAL KIT 6017945)
1. The z-purlin mounting kit is available from Entrematic.
Consult a structural engineer prior to installation.
2. Using the z-purlin backer plate as a template, locate and
mark the holes in the z-purlins for both opposing mounts.
3. Attach the z-purlin brackets to the z-purlins. Torque to
20-28 ft-lbs. See Fig. 6.
4. Cut angle irons to required length and install, spanning
the z-purlin mounts using the supplied hardware. Torque
to 20-28 ft-lbs. See Fig. 6.
5. Using the fan mount as a template, mark and drill four
7/16" dia. holes into the spanned angle irons.
6. Mount bracket to the angle irons using the supplied 3/8"
x 1" grade 5 screws and nuts. Torque to 20-28 ft-lbs. See
Fig 6.
Fig. 6