© Entrematic
Group AB 2015
November 2016
6020031A — Commercial HVLS Fans
7
INSTALLATION CONSIDERATIONS
NOTE:
Angle mount has 45° of motion. The
extension lengths shown are minimum
recommendations only, based solely of roof
pitch and fan diameter. Other considerations
must be evaluated when determining
extension requirements, such as placement
of lights, sprinkler systems, HVAC systems,
etc. In addition, OSHA requirements state
that fan blades must be a minimum of 10'
above the floor.
Fig. 2
36" exclusion zone
(18" radius)
[both sides]
36" min.
(to wall)
10' min.
(to floor)
Do not mount directly under or within exclusion zone or
in line with HVAC supply discharge vent.
Fan Size Extension size (Ft) Max Roof Angle Allowable (degrees)
6Ft
1.5
17
6Ft
2
20
6Ft
3
35
6Ft
4
40
8Ft
1.5
10
8Ft
2
15
8Ft
3
25
8Ft
4
32
10Ft
1.5
10
10Ft
2
12
10Ft
3
19
10Ft
4
28
12Ft
1.5
8
12Ft
2
10
12Ft
3
17
12Ft
4
25
14Ft
1.5
6
14Ft
2
8
14Ft
3
15
14Ft
4
21