6
Connection Diagram
1- Voltage Inputs
3- Auxiliary Supply Input
5- RS-485
4- Current Inputs
2- Relay Outputs
Terminal Structure;
Connection
Range
Klemens Tipi
1
Voltage Inputs
3 x 10 – 480 VAC 50/60Hz
4 x 7.62 mm socket
2.5 mm², 4 mm²
2
Relay Outputs
2 x 250 VAC 5A 1250 VA
4 x 5.08 mm socket
2.5 mm² / 4 mm²
3
Auxiliary supply input
100-270 VAC / 50-60 Hz
3 x 5.08 mm socket
2.5 mm² / 4 mm²
4
Current Inputs
3 x 0.05 – 5.5A / AC 50-60 Hz
6 x 5.08 mm socket
2.5 mm² / 4 mm²
5
RS-485
Max. ±12V
3 x 3.81 mm socket
1.5 mm² / 2.5 mm