Section 78 

 

00-02-0997 (web only) 

2019-10-07 

- 17 - 

Inputs 

Follow these steps to change the Inputs: 

1. 

Press 

 to display the Menu. 

2. 

Press 

 

to System Settings.  Press 

 to enter. 

3. 

Utilize keys 1, 2 and 3 to input the password (3482) and key 5 to enter. 

4. 

Arrow to highlight Inputs.  Press 

 to enter.   

5. 

Highlight the appropriate Resistive Input and press 

 to enter.  

6. 

Choose the appropriate Function, Sender, Fault and Set Point for each Resistive 
Input. 

7. 

Press 

 to return to the previous Menu 

8. 

Highlight with the arrow keys the Analog input and press 

 to enter 

9. 

Choose the appropriate Function, Sender, Fault and Calibration for each Analog 
Input.  

10. 

Press 

 to return to the Menu. 

 

Output 2 

Follow these steps to change the Output 2: 

1. 

Press 

 to display the Menu. 

2. 

Press 

 

to System Settings.  Press 

 to enter. 

3. 

Utilize keys 1, 2 and 3 to input the password (3482) and key 5 to enter. 

4. 

Arrow to highlight Output 2.  Press 

 to choose Disabled, Comm Alarm or Air 

Shutoff.   

 

Comm Alarm:  When the Digital Output 2 is configured as Comm Alarm, Digital 
Output 2 will turn ON for any CAN or internal diagnostic shut-down message.  
Digital Output 2 will turn back OFF when all the shut-down messages are cleared. 
 
Air Shutoff:  The Digital Output 1 is disabled, the Digital Output 2 is turned on, and 
an internal Diagnostic Message (red lamp) is displayed when the following 
conditions are met: 
 

  Air Shutoff is chosen 

  Throttle is Enabled 

  Pressure Shutdown, Temp Shutdown or Overspeed Shut (Type of Shutdown) 

is chosen 

  Engine speed is greater than Overspeed Shutdown or 100 RPM more than the 

target speed 

5. 

Press 

 to return to the Menu. 

Содержание Murphy PowerView PV380-R2

Страница 1: ...ection 78 PowerView PV380 R2 Murphy Standard Configuration Operations Manual Products covered in this document comply with European Council electromagnetic compatibility directive 2004 108 EC and electrical safety directive 2006 95 EC ...

Страница 2: ...onsistently bring you the highest quality full featured products we reserve the right to change our specifications and designs at any time The latest version of this manual can be found at www enovationcontrols com ...

Страница 3: ...unctions 3 First Time Startup 6 Parameter Gauge Settings 8 Adjusting Menu Selections 9 User Settings 9 Service Reminders 12 Regen 13 Set Points 14 Software Version 14 System Settings 15 Faults 21 Diagnostics and Service 21 LED Indicators 21 Indicator Lamps 22 Supported PGNs 22 Specifications 26 ...

Страница 4: ... THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 5: ...nlight Engine and Transmission Parameters The following are some of the engine and transmission parameters that can be displayed in standard units Engine Speed Engine Temperature Engine or Machine Hours of Operation Total Machine Hours Battery Voltage Coolant Temperature Engine Oil Pressure Engine Fuel Level Discharge Pressure Suction Pressure Diesel Exhaust Fluid DEF Level Tier 4 only Active Faul...

Страница 6: ...ght up when in certain Menu selections Decreases the number when in various screens Key 2 Function FAULTS Displays Diagnostic Messages Faults and Stored Codes Moves highlight down when in certain Menu selections Increases the number when various screens Key 3 Function Displays the Main Menu entrance point Serves as the Escape Return to Previous Menu button ...

Страница 7: ...sor one slot at a time to the right Key 5 Function Increases the Throttle set point ACTIVE FAULTS Displays the Active Faults Serves as the Enter key for menu selections Increases various settings Moves the cursor to the next cell when customizing parameters on the home screen Moves the cursor one slot at a time to the right and displays alternate menu choices screens ACK Acknowledges active faults...

Страница 8: ...ansmitting the wait to start message or if the engine speed is 500 RPM If the ECU never transmits the wait to start message the splash screen is displayed for three seconds after key on then the main gauge screen is shown Once the engine is running 500 RPM the engine information electronic or mechanical will display on the main gauge screen and additional parameters on the second screen The second...

Страница 9: ...Section 78 00 02 0997 web only 2019 10 07 7 Main gauge screen Electronic Second gauge screen Electronic Main gauge screen Mechanical Second gauge screen Mechanical ...

Страница 10: ...ive Displays when High Exhaust System Temperature HEST is active and exhaust temperature is above normal operating condition Regen Inhibit Regen Inhibit is restricted when a HEST alarm is present displays when the engine ECU has inhibited a regeneration or a manual inhibit has been requested Displays when engine after treatment requires regeneration This is as a result of the after treatment filte...

Страница 11: ...ltage Fuel Level DEF Level Tier 4 only Target Speed when SCR is disabled NOTE Target Speed gauge appears for 5 seconds when the user throttles the engine see arrow above 4 Button Selection Display The button functions can change depending on the screen displayed Adjusting Menu Selections NOTE Once parameters are changed back out of all menus and initiate a power cycle for changes to take effect Us...

Страница 12: ...o enter then arrow to LANGUAGE 3 Press to cycle through the available languages English French German Spanish and Italian 4 Press to save and exit the menu Units Follow these steps to adjust the Units 1 Press to display the Menu 2 Arrow to USER SETTINGS Press and then arrow to UNITS 3 Press to choose US STD Metric KPA or Metric BAR 4 Press to save and exit the menu ...

Страница 13: ... To adjust the minutes press and the cursor will move to the right 5 Repeat steps 3 and 4 to adjust the minutes and seconds 6 Press to save and exit the menu Date Follow these steps to adjust the Date 1 Press to display the Menu 2 Arrow to USER SETTINGS Press and then arrow to DATE 3 Press and to adjust the day 4 Press and the cursor will move to the month 5 Repeat steps 3 and 4 to adjust the mont...

Страница 14: ... and then arrow to CLOCK 3 Press to alternate between SHOW and HIDE 4 Press to save and exit the menu Service Reminders Available service reminders Engine Oil Fuel Filter Engine Air Filter Hydraulic Oil Service Engine and Service Machine Press to display the Menu 1 Press to Service Reminders Press to enter 2 Press or to scroll through the read only screens ...

Страница 15: ...ss to enter 3 If the engine ECU has inhibited a regeneration the Regen Mode will display the current mode of the engine regeneration as Inhibit 4 The AUTO REGEN button will be available to switch the engine to automatically regenerate 5 If the engine ECU is currently on AUTO regeneration the Regen Mode will display the current mode of the engine regeneration as Auto 6 The INHIBIT REGEN button will...

Страница 16: ...Shutdowns and the specified criteria Press to view the second screen listing Warnings and the specified limits Software Version To display the software version information useful for Enovation Controls personnel to identify which configuration the customer is using follow these steps 1 Press to display the Menu 2 Arrow to Software Version and press The following screen will appear 3 Press to exit ...

Страница 17: ...Mechanical engine types NOTE Selecting Electronic engine type will enable the Throttle menu to appear in System Settings The Throttle menu is disabled for Mechanical engine type 2 See the table below to configure remaining settings Engine Type Configurable Settings Electronic DPF Default enabled SCR Default enabled ECU Source Address Default ALL Display Source Address Default 43 Overspeed o Shutdo...

Страница 18: ...owing to configure throttle settings System Setting Specific Parameters Available Throttle Throttle Default enabled o Throttle Type Display Default Switch Resistive Input 1 will be Throttle Switch UP Resistive Input 3 will be Throttle Switch DOWN Knob Resistive Input 1 will be disabled Resistive Input 3 will be Throttle Knob o Throttle Mode For Types Display and Switch Manual Preset For Type Knob ...

Страница 19: ... change the Output 2 1 Press to display the Menu 2 Press to System Settings Press to enter 3 Utilize keys 1 2 and 3 to input the password 3482 and key 5 to enter 4 Arrow to highlight Output 2 Press to choose Disabled Comm Alarm or Air Shutoff Comm Alarm When the Digital Output 2 is configured as Comm Alarm Digital Output 2 will turn ON for any CAN or internal diagnostic shut down message Digital O...

Страница 20: ...ize press The check mark will move 10 Repeat steps 8 and 9 until all gauges have been customized Press to return to the Menu 11 Highlight Engine Speed Dial and press to alternate between 3000 4000 and 6000 RPM 12 Highlight Hour Meter Type and press to alternate between Engine Hours and Machine Hours NOTE If the type is set to Engine Hours the unit must be connected to an ECU and be receiving data ...

Страница 21: ... to adjust the hours Each press of the button will decrement or increment the hours by 10 7 Highlight Hour Type and press or to alternate between Engine Hours and Machine Hours 8 To simply reset the hours highlight Reset and press OK 9 Press to be returned to the System Settings menu Advanced Settings Follow these steps to enter and review the Advanced Settings 1 Press to display the Menu 2 Press ...

Страница 22: ...3 Stability Optimized for driveline engaged and or in lockup condition 2 PTO driveline The above descriptions taken from SAE International document J1939 71 May2012 897 Override Control Mode Priority 0 Highest Priority 1 High Priority 2 Medium Priority 3 Low Priority 3349 TSC1 Transmission Rate 0 1000 mS 1 750 mS 2 500 mS 3 250 mS 4 100 mS 5 50 mS 6 20 mS 7 10 mS 8 To configure the JD Lockout repe...

Страница 23: ...the Stored Codes press Stored Codes Stored codes are requested from the ECU While the data is being requested REQUESTING and RECEIVING DATA will be displayed If data is not received from the ECU TIMEOUT will be displayed Pressing Stored Codes once more will request data from the ECU again If data is received the Diagnostic Message screen of will appear Press the and to scroll through additional me...

Страница 24: ... Particulate Filter Restricted Lamp indicates a Regen is needed 64892 3703 DPF Inhibit Lamp indicates an inhibited Regen status 65110 1761 Diesel Exhaust Fluid DEF Lamp displays when the fluid level drops below 12 Service Indicator 65110 5246 Engine Emissions System Failure Supported PGNs The following table of parameters shall be available for selections based on being actively broadcast on the C...

Страница 25: ...mperature 65262 13 Engine Intercooler Temp 65262 INTC TEMP 14 Fuel Delivery Pressure 65263 15 Engine Oil Level 65263 16 Engine Oil Pressure 65263 17 Coolant Pressure 65263 18 Coolant Level 65263 19 Wheel Based Vehicle Speed 65265 VEH SPD 20 Fuel Rate 65266 FUEL RATE 21 Instantaneous Fuel Economy 65266 FUEL ECON 22 Average Fuel Economy 65266 AVG ECON 23 Barometric Pressure 65269 BARO PRES 24 Air In...

Страница 26: ... Drive 65213 35 Auxiliary Temperature 65164 AUX TEMP 36 Auxiliary Pressure 65164 AUX PRES 37 Selected Gear 61445 SLECT GEAR 38 Current Gear 61445 CURNT GEAR 39 Output Shaft Speed 61442 OUT SFT SP 40 Input Shaft Speed 61442 IN SFT SPD 41 Torque Converter Lockup 61442 TORQ LOCK 42 Auxiliary IO Status 1 65241 AUX IO 1 43 Accelerator Pedal Switch 61443 PEDAL SWT 44 Engine Desired Op Speed 65247 DES EN...

Страница 27: ...ar 65256 REQ GEAR 50 Fuel Level 65276 51 Hydraulic Pressure 61448 52 Hydraulic Temp 65128 53 Machine Hours 61444 54 Diesel Exhaust Fluid Level 65110 DEF LVL 55 Soot 64891 SOOT 56 Ash 64891 ASH 57 Exhaust Filter Temp 64947 58 Exhaust Filter Inlet Temp 64948 59 Discharge Pressure Analog Input 1 60 Suction Pressure Analog Input 2 ...

Страница 28: ... tactile buttons Input 4 resistive analog 3 analog 0 5V 4 20 mA 1 frequency 2 10 000Hz 3 6 120VAC Output 2 500mA switched low side Voltage 6 36 VDC reverse polarity protected Environmental Operating Temperature 40º C to 85º C 40 F to 185 F Storage Temperature 40º C to 85º C 40 F to 185 F Protection IP66 and 67 IEC EN 60529 Standards Compliance Electrical Safety 2006 95 EC Electromagnetic Compatibi...

Страница 29: ...Section 78 00 02 0997 web only 2019 10 07 27 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 30: ......

Отзывы: