Inputs
Follow these steps to change the Inputs:
1.
Press
to display the Menu.
2.
Press
to System Settings. Press
to enter.
3.
Utilize keys 1, 2 and 3 to input the password (3482) and key 5 to enter.
4.
Arrow to highlight Inputs. Press
to enter.
5.
Highlight the appropriate Resistive Input and press
to enter.
6.
Choose the appropriate Function, Sender, Fault and Set Point for each Resistive
Input.
7.
Press
to return to the previous Menu
8.
Highlight with the arrow keys the Analog input and press
to enter
9.
Choose the appropriate Function, Sender, Fault and Calibration for each Analog
Input.
10.
Press
to return to the Menu.
Output 2
Follow these steps to change the Output 2:
1.
Press
to display the Menu.
2.
Press
to System Settings. Press
to enter.
3.
Utilize keys 1, 2 and 3 to input the password (3482) and key 5 to enter.
4.
Arrow to highlight Output 2. Press
to choose Disabled, Comm Alarm or Air
Shutoff.
Comm Alarm: When the Digital Output 2 is configured as Comm Alarm, Digital
Output 2 will turn ON for any CAN or internal diagnostic shut-down message.
Digital Output 2 will turn back OFF when all the shut-down messages are cleared.
Air Shutoff: The Digital Output 1 is disabled, the Digital Output 2 is turned on, and
an internal Diagnostic Message (red lamp) is displayed when the following
conditions are met:
Air Shutoff is chosen
Throttle is Enabled
Pressure Shutdown, Temp Shutdown or Overspeed Shut (Type of Shutdown)
is chosen
Engine speed is greater than Overspeed Shutdown or 100 RPM more than the
target speed
5.
Press
to return to the Menu.