![EnOcean B6221-K516 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/enocean/b6221-k516/b6221-k516_user-manual_2413678043.webp)
USER MANUAL
STM 550B / EMSIB - EASYFIT MULTISENSOR FOR IOT APPLICATIONS (2.4 GHZ BLE)
© 2020 EnOcean | www.enocean.com
F-710-017, V1.0
STM 550B / EMSIB User Manual | v1.3 | June 2020 | Page 43 / 115
5.5.3
Data Size
The following values are possible for the Data Size field:
◼
0b00 = 8 bit size (or implicit definition, e.g. commissioning telegram = 22 byte)
◼
0b01 = 16 bit size
◼
0b10 = 32 bit size
◼
0b11 = Extended size, the size is specified in the first byte of the Sensor Data field
5.5.4
Supported parameters
STM 550B can report a variety of parameters depending on the product configuration. Pa-
rameter reporting can be configured via the REPORTING_CFG register of the NFC configura-
tion interface as described in chapter 9.5.15 .
Keep in mind that the combined parameter length of all items cannot exceed 19 byte due to
the BLE Frame structure as shown in Figure 27. Each parameter requires 1 byte Type ID in
addition to the Data Length shown in Table 6 below. It is therefore not possible to report all
supported parameters.
Table 6 below summarizes the parameters that can be reported by STM 550B and notes the
ones that are enabled by default. Please refer to Appendix A for examples of how to interpret
an STM 550B data and an STM 550B commissioning telegram.
TYPE
ID
Size Content
Min
Value
Max
Value
Res
Encoding
Default
Reporting
Data Telegrams
0x00 2
Temperature
-327.67°C
327.66°C
0.01
°C
16 bit
signed int
Enabled
0x01 2
Voltage
-16383.5mV 16383 mV 0.5
mV
16 bit
signed int
Adaptive
0x02 1
Energy Level
0%
100%
0.5
%
8 bit unsigned
int (0 … 200)
Adaptive
0x04 2
Illumination
(Solar cell)
0 lx
65 533 lx
1
lx
16 bit
unsigned int
Disabled
0x05 2
Illumination
(Sensor)
0 lx
65 533 lx
1
lx
16 bit
unsigned int
Enabled
0x06 1
Relative
Humidity
0 % r.h.
100 % r.h. 0.5
% rh
8 bit unsigned
int (0 …
200)
Enabled
0x0A 4
Acceleration
Vector
See Table 3 and Table 4
Enabled
0x23 1
Magnet
Contact
0x01 = Open, 0x02 = Closed
Enumeration
Enabled
0x3C 1, 2,
4
Optional Data
User-defined data
Disabled
Commissioning Telegrams
0x3E 22
Commissioning
Info
16 byte AES key followed by 6 byte advertising
address
LRN button
Table 6
–
Supported parameters