![EnOcean B6221-K516 Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/enocean/b6221-k516/b6221-k516_user-manual_2413678080.webp)
USER MANUAL
STM 550B / EMSIB - EASYFIT MULTISENSOR FOR IOT APPLICATIONS (2.4 GHZ BLE)
© 2020 EnOcean | www.enocean.com
F-710-017, V1.0
STM 550B / EMSIB User Manual | v1.3 | June 2020 | Page 80 / 115
9.5.27
ACCELERATION_TX_INTERVAL
If acceleration-controlled reporting has been enabled and the acceleration exceeds the de-
fined acceleration threshold then the resulting reporting interval will be determined by the
register ACCELERATION_TX_INTERVAL shown in Figure 63 below.
ACCELERATION_TX_INTERVAL (Default Setting: 0x003C)
Bit 15
Bit 14
…
Bit 1
Bit 0
ACCELERATION INTERVAL
Figure 59
–
ACCELERATION_TX_INTERVAL register
The encoding used by the ACCELERATION INTERVAL bit field is shown in Table 49 below.
ACCELERATION INTERVAL
Acceleration-based reporting interval
0x0000, 0x0001, 0x0002
Not supported (Do not use)
0x0003
3 seconds (minimum setting)
…
…
0x003C (Default)
60 seconds (default setting)
…
…
0xFFFF
65535 seconds (maximum setting)
Table 45
–
ACCELERATION INTERVAL bit field encoding
The default reporting interval when the acceleration meets the defined threshold criteria is
60 seconds. This can be reduced according to user requirements keeping in mind the en-
ergy balance.