2.3.2
Standard reporting interval
The standard reporting interval determines the longest interval between two status updates
of STM 550B, i.e. the minimum update rate.
STM 550B can be configured to use a lower reporting interval, i.e. a higher update rate, based
on acceleration and available light as described below. But under no circumstances will STM
550B report with a longer reporting interval, i.e. a lower update rate, than the standard
reporting interval.
The default setting for the standard reporting interval is one status update once every 60
seconds (1 minute). This means that STM 550B will at least report its status once every 60
seconds while sufficient energy is available.
The standard reporting interval can be adjusted using the STANDARD_TX_INTERVAL NFC
register as described in chapter 9.5.18. Consider the available energy before lowering the
reporting interval as discussed in chapter 2.3.1.
Figure 2 below illustrates the use of the standard reporting interval.
STANDARD_TX_INTERVAL
STANDARD_TX_INTERVAL
Figure 2
–
Standard reporting interval