Programming the Output Mode and Output Timing:
The relays for outputs #1, #2, and #3 can be programmed to trigger ON and OFF with a user code
or user card (toggle mode), or to trigger for a programmed length of time of up to nearly 28 hours
before automatically turning OFF. The toggle or timed outputs can be used for locking or unlocking
a door or for a variety of functions that can be controlled with the keypad.
When programming the output mode and time, use this general formula:
– Output
– Output Mode and Time
Outputs:
•
–
Output #1
•
–
Output #2
•
–
Output #3
Output Mode and Time:
•
–
Start/stop (toggle) mode. In this case, the output starts when a user code and/or user card
is entered, and stops when a user code and/or card is entered.
•
to
–
The output triggered by a user code and/or user card lasts 1 to 99,999
seconds (nearly 28 hours) before automatically turning off (default 5 seconds).
NOTE:
While the keypad is in momentary timed output mode, the output can be reset any time by
entering the super user code.
Examples
(in these examples, assume that the super user code is
)
:
1.
In programming mode, set the output #1 to toggle:
2.
In programming mode, set the output #2 to 60 seconds:
3.
Reset output #1 timer:
4.
Reset output #2 timer:
5.
Reset output #3 timer: