background image

 

 

0

T≤2 

10 

-3.2 

-2

T≤0 

15 

-5.4 

-4

T≤-2 

20 

-7.8 

-7

T≤-4 

25 

-10.7 

-11

T≤-7 

30 

-14.1 

-14

T≤-11 

35 

-17.9 

-19

T≤-14 

40 

-22.3 

-24

T≤-19 

45 

-27.5 

-31

T≤-24 

50 

-33.8 

-31

T≤-29 

60 

-34.7 

Remarks:  The  mass  percentage  concentration  C%=the  mass  of  the  solute/the  ma

ss  of  the 

solution. The example shows that the historically lowest ambient temperature in Shanghai, China is 

-12.1

.  Check  the  table  above,  and  45kg  of  glycerol  should  be  added  to  the  100kg  antifreeze 

mixture  as  antifreeze,  or  100kg  of  antifreeze  mixture  needs  to  add  40kg  of  ethylene  glycol  as 

antifreeze. 

 

2.  Trouble shooting 

Phenomenon 

Reasons 

Solutions 

The unit doesn’t work. 

1.No power supply. 

1.Please wait for the power supply. 

2.Power switch not on. 

2.Open up the power switch. 

3.Power switch fuse blown. 

3.Replace fuse. 

4.The timing time is not up. 

4.Please wait or cancel the timing settings. 

The unit does not work 

when turns on. 

1.Compressor protection interval not 

reached. 

1.Please wait the protection time to end patiently. 

2.The unit water temperature does not reach 

the starting water temperature. 

2.It is normal phenomenon, wait for the starting 

water temperature. 

The unit works 

normally, but the hot 

water temperature is 

low. 

1.Improper temperature setting. 

1.Set proper temperature. 

2.Excessive hot water consumption. 

2.Wait the hot water to warm up before using it. 

3.The air inlet or outlet of outdoor unit or 

indoor unit is blocked. 

3.Remove the obstruction from the air inlet or 

outlet. 

The unit turns on 

automatically. 

1.The timing time is up. 

1.If you do not want to use it, please turn off the 

unit or cancel the timing settings. 

Abnormal sound of the 

unit. 

1.There is too much dust or obstruction on 

the air inlet of the unit evaporator, produce 

strong and weak sound of wind. 

1.Remove the dust or obstructions from the unit 

evaporator. 

2.The Refrigerant flow may produce some 

noise when the unit turns on or turns off. 

2.It is normal phenomenon. 

3.No power on,    the unit rings like 'dada'    .  3.It is normal phenomenon, reset of EEV. 

 

Содержание BC-F20HWR2-200L

Страница 1: ...DOMESTIC INTEGRATED HEAT PUMP WATER HEATER Installation Instruction Manual MODELS BC F20HWR2 200L ...

Страница 2: ......

Страница 3: ...Content I Foreword 1 II Operation Instruction 2 III Maintenance and Trouble Shootings 5 IV Technical Parameters 8 V Installation 10 VI Circuit Specification and Wiring Diagram 12 VII Wi Fi Function 14 ...

Страница 4: ...is filled with water Do not put the inflammable and explosive material near the unit Do not repair maintain dismantle or transform the unit without permission Do not touch the plug with wet hands Do not put your hands or anything s close to the air outlet and blades In case of unit abnormality please cut off the power supply immediately and contact our personnel for handling Safety notice It may c...

Страница 5: ...g place Do not cut off the power supply plugs to turn off the heat pump II Operation Instruction 1 Panel Sign Description Sign Name Sign Name Sign Name ON OFF key BATH sign ERROR sign TIME key CYCLIC VENTILATION sign STANDBY TIMING key ELECTRIC HEATER key ELECTRIC HEATER sign SETTING key ...

Страница 6: ...uch the SETTING key and STANDBY TIMING key for 5s to enter forced manual defrost mode 5 Temperature Adjustment Press the SETTING key 5S to enter the system parameter query and query each parameter by combining the UP key and DOWN key In the system query parameter state press the SETTING key to set the parameter and set each parameter by combining the UP key and DOWN key The parameter serial number...

Страница 7: ...ater symbol lamp will be on 9 Ventilation mode Long press the ELECTRIC HEATER key to enter and exit the ventilation mode 10 Restore defaults In the shutdown state long press the ELECTRIC HEATER key and SETTING key to restore factory setting parameters 11 Set system parameter In any state press SETTING key for 5 seconds enter the system parameter query interface with UP key and DOWN key to query ea...

Страница 8: ...lower than 2 anti freeze valves and pipelines shall be installed in the solar coil water channel and filled with anti freeze liquid such as glycerin aqueous solution or ethylene glycol aqueous solution l Note If the ambient temperature is lower than 2 please install circulating water pump on the customer s water side to avoid freezing of pipeline during use When the machine is out of order the wat...

Страница 9: ...n interval not reached 1 Please wait the protection time to end patiently 2 The unit water temperature does not reach the starting water temperature 2 It is normal phenomenon wait for the starting water temperature The unit works normally but the hot water temperature is low 1 Improper temperature setting 1 Set proper temperature 2 Excessive hot water consumption 2 Wait the hot water to warm up be...

Страница 10: ... Heating return difference temperature 2 15 5 Adjustable 2 Electric auxiliary heat start water tank temperature TS2 10 85 65 Adjustable 3 Delay time of the electric auxiliary heater t1 0 90 1min Adjustable Real time setting value 5 4 Electric auxiliary heater high temperature disinfection stop temp 50 75 75 Adjustable 5 High temperature disinfection maintenance time t2 0 90min 30min Adjustable 6 H...

Страница 11: ...xpansion valve set 2 45 40 10P Adjustable 20 Expansion valve allowed exhaust temperature 70 120 100 Adjustable 21 Ambient temperature when allow defrosting 0 50 15 Adjustable 22 Temperature difference between ambient and coil when start defrosting 1 20 2 Adjustable 23 Exhaust high temperature protection value 50 110 105 Adjustable 24 Compressor running time when start electric heater 1 24hours 10h...

Страница 12: ...L h 33 Water Connection inch G3 4 Noise dB A 55 Operation Temp Range 30 43 Refrigerant R134a Net Weight kg 110 Net Dimensions L W H mm Φ570 1871 The parameters in the table are nominal values according to the rated working condition specified in EN 16147 which will change with working condition The above parameters are subject to product nameplate if changed due to the product upgrade please kindl...

Страница 13: ...0 V Installation 1 Reservation Space The minimum space required by the upward air outlet heat pump unit 2 Installation Schematic Diagram WITH backwater control function WITHOUT backwater control function ...

Страница 14: ...wnward manner in a frost free environment l The connection between the unit and the water pipe must be equipped with cut off valves or removable loose connections l Water tank emptying operation close the water replenishing valve open the sewage gate valve and connect the water in and out of the water tank Watch out for burns l For the area where the historical minimum ring temperature is lower th...

Страница 15: ... not be used and the power cord used shall not be lighter than the neoprene armored flexible cord line 57 in IEC 60245 The wire diameter specification of power cord air circuit breaker leakage circuit breaker and load current comparison table Distribution Device And Power Cord of The Heat Pump Unit Maximum current of heat pump units A Wire cross section mm Tripping current of air circuit breaker A...

Страница 16: ...tch on the power supply after carefully checking 2 Wiring Diagram The connection methods between the units and power supply and the interconnection methods of each individual part should be according to the wiring diagram on the unit ...

Страница 17: ...are Installation Method 1 Search Smart life in your APP store install Click GET to install Method 2 Scan the QR code below For IOS and Android Users 2 Software Startup After installation click on your desktop to start up Smart Life ...

Страница 18: ...n Users don t have account can click Register to create an account Register Enter your phone number Get Verification Code Enter Verification Code Set Password After registration you need to Create a Home Create a Home Set Home Name Set Home Location Add Rooms ...

Страница 19: ...16 2 Account ID Password Login Existing accounts can be logged in directly in the following order ...

Страница 20: ...forget your password you can choose to login with your verification code and select Forget Password Enter your phone number Get verification code After creating a home or logged in enter the main interface of APP ...

Страница 21: ... is connect successfully the icon will not appear Step 2 Turn on the phone s Wi Fi function and connect to the Wi Fi hot spot The Wi Fi hot spot must be able to connect to the Internet normally Step 3 Open the smart life APP log in into the main interface click on the top right corner or add equipment of the interface enter the equipment type selection the Large Home Appliances select Water Heater...

Страница 22: ...has selected the EZ mode After the indicator light under flashes rapidly click Confirm indicator rapidly blink Enter the Wi Fi connection interface enter the Wi Fi password of the mobile phone it must be the same as the Wi Fi of the mobile phone click Next and then directly enter the connected status of the device ...

Страница 23: ...20 Step 5 When Scan devices Register on Cloud Initialize the device are all completed connect succeeds ...

Страница 24: ...ce click EZ Mode in the upper right corner Enter the AP mode to add the device interface confirm that the AP mode has been selected and click Confirm indicator slowly blink The interface of Wi Fi connection will pop up enter the Wi Fi password of the mobile phone it must be the same as the Wi Fi of the mobile phone click Next Connect your mobile phone to the device s hot spot will pop up and click...

Страница 25: ...22 Enter the mobile phone Wi Fi connection interface find the SmartLife_XXXX connection and the APP will automatically enter the device connection status ...

Страница 26: ...interface Back More You can change device name select device installation location check networking status add Shared users create device cluster view device information and more Setting temperature adjustment The white circle slides counterclockwise to reduce the temperature but clockwise to increase the temperature Target temperature Current temperature Mode switching Click to select the mode to...

Страница 27: ...e user should do so in the following order u After successful sharing the list will be added to show the person shared u If you want to delete the account you shared to cross the selected account to the left and delete it u The user interface is as follows ...

Страница 28: ...e shared click Done and the share success list shows the newly added account of the Shared u The interface of the person to be shared is as follows The received shared device is displayed Click it to operate and control the device ...

Страница 29: ...26 l Mode settings Click on the main interface to switch modes select what you need ...

Страница 30: ... on the main interface to enter timer setting interface as shown below click to add timer 2 After entering timer setting swipe up down to set timer set up repeat weeks and on off then click save to save your settings as follows ...

Страница 31: ...corner of the main interface to enter the device details interface and click device removal to enter EZ mode Indicator light under flashes rapidly for 3min The network can be reconfigured within 3 minutes and the network can be quit if it is not connected within 3 minutes The specific operations are shown as follows ...

Страница 32: ...29 ...

Страница 33: ...30 ...

Отзывы: