Handbuch-KnxSmartmeter-85A-en-3.odt, 2018-10-04
Seite 68 von 69
ID
Name
Object function
Length
Type
Flags
155 Tariff 1
Rate (0.01ct/kWh)
2 Byte
[8.001]
DPT_Value_2_
Count
CRWT-
When writing to this object, the rate of tariff 1 in 0.01ct is adopted from the bus. If the parameter “Adopt rate from the
bus” is set on “flighty” then the rate adopted from the bus is discarded after the next reset of the intermediate counter.
If in contrast the parameter is set on “permanent” then the rate adopted from the bus is permanent.
ID
Name
Object function
Length
Type
Flags
156 Tariff 2
Trigger (Tariff start)
1-Bit
[1.017]
DPT_Trigger
C-W--
If the parameter “By trigger objects” in “Tariff switch tariff 2” is set, then tariff 2 is started when receiving this object.
The value of the object is not taken into account.
ID
Name
Object function
Length
Type
Flags
157 Tariff 2
Trigger (Tariff stop)
1-Bit
[1.017]
DPT_Trigger
C-W--
If the parameter “By trigger objects” in “Tariff switch tariff 2” is set, then tariff 2 is stopped when receiving this object.
The value of the object is not taken into account.
ID
Name
Object function
Length
Type
Flags
158 Tariff 2
Rate (0.01ct/kWh)
2 Byte
[8.001]
DPT_Value_2_
Count
CRWT-
When writing to this object, the rate of tariff 2 in 0.01ct is adopted from the bus. If the parameter “Adopt rate from the
bus” is set on “flighty” then the rate adopted from the bus is discarded after the next reset of the intermediate counter.
If in contrast the parameter is set on “permanent” then the rate adopted from the bus is permanent.
ID
Name
Object function
Length
Type
Flags
159 Tariff 3
Trigger (Tariff start)
1-Bit
[1.017]
DPT_Trigger
C-W--
If the parameter “By trigger objects” in “Tariff switch tariff 3” is set, then tariff 3 is started when receiving this object.
The value of the object is not taken into account.
ID
Name
Object function
Length
Type
Flags
160 Tariff 3
Trigger (Tariff stop)
1-Bit
[1.017]
DPT_Trigger
C-W--
If the parameter “By trigger objects” in “Tariff switch tariff 3” is set, then tariff 3 is stopped when receiving this object.
The value of the object is not taken into account.
ID
Name
Object function
Length
Type
Flags
161 Tariff 3
Rate (0.01ct/kWh)
2 Byte
[8.001]
DPT_Value_2_
Count
CRWT-
When writing to this object, the rate of tariff 3 in 0.01ct is adopted from the bus. If the parameter “Adopt rate from the
bus” is set on “flighty” then the rate adopted from the bus is discarded after the next reset of the intermediate counter.
If in contrast the parameter is set on “permanent” then the rate adopted from the bus is permanent.
Communication flags according to the KNX specification with the following functions:
•
C = communication: bus communication possible
•
R = read: allows reading a value from the group object
•
W = write: allows writing a value to the group object
•
T = transmit: allows transmitting a value (usually this flag indicates the transmitting GA)
•
U = update: allows updating a value of a group object with any feedback ("listen and
synchronize" - functionality)