enertexbayern Enertex KNX Smartmeter 85A (RT) Скачать руководство пользователя страница 48

Handbuch-KnxSmartmeter-85A-en-3.odt, 2018-10-04                                             

Seite 48 von 69 

Name

Options

Description

Count interval

[1min, 5min, 10min, 15min, 1h, 12h, 24h, 
1 week, via trigger object]

The count interval can be selected here. After the 
selected time the intermediate counter is reset. 
Before resetting the current intermediate counter 
reading is copied to the group object of the 
previous value. The reset time instances of a 
intermediate counter are synchronized with the 
time, that is e.g.at time interval of 1 min the 
counter is reset each when the second indicator 
of the clock is 0. At 15 min counting interval the 
counter value is reset corresponding to each 
synchronized 1/4 hour, that is e.g. 00:00, 00:15, 
00:30, 00:45. 
Note: Since intermediate counters are 
synchronized with the time, the counter readings 
only reset at the defined times (and automatically 
transmitted on the bus), if a time has been 
transmitted to the group object “time” of the 
Smartmeter. 
If the value is set “on trigger object” then the 
corresponding object is released. If in this case 
the value ON is transmitted to the trigger group 
object “Reset counter value”, then this has the 
same effect as reaching the interval limit in the 
above case.

Transmit counter 
value before resetting

[Yes / No]

After updating the group object “previous. value” 
at a count interval limit, this group object is 
transmitted automatically on the bus. The 
message is delayed in accordance with the 
parameter of “General offset when transmitting 
intermediate counter values”

Transmit counter 
values cyclically 
(x10s)

[0,1,2...17280, 0 = not transmit cyclically]

The counter value of the group object “Current 
value” can be transmitted cyclically.

Message at limit 
value

[Yes / No]

When exceeding or falling below the limit value of 
the intermediate counter a group object can be 
transmitted. Release of the limit parameter and of 
the group object. See also section Message of
limit values

Adopt limit value from 
bus

[flighty / permanent]

The limit value, adopted by the bus, can either be 
valid only until the next reset or override the 
configured value permanently.

Limit value (Wh)

[-32767, -32766, ... -1, 0, 1 ... +32767]

Limit of the intermediate counter. This parameter 
is only enabled when the counted value of the 
intermediate counter is an energy counter.

Limit value(Cent)

[-32767, -32766, ... -1, 0, 1 ... +32767]

Limit of the intermediate counter. This parameter 
is only enabled when the counted value of the 
intermediate counter is a cost counter.

Tariff

Under the tab “Tariff” the following settings can be made:

Figure 36: Parameter Tariff

Enertex

®

 Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - Deutschland - [email protected]

Содержание Enertex KNX Smartmeter 85A (RT)

Страница 1: ...by Enertex Bayern GmbH Enertex is a registered trademark of Enertex Bayern GmbH Other product and company names mentioned herein can be names of trademark or registered trademarks of their respective...

Страница 2: ...for Photovoltaics 16 Measurement quantities 23 General Function Concepts 25 Cyclical transmitting 25 Transmit at Change 25 Bidirectional Counter 26 Intermediate Counter 27 Tariff Costs Counter 27 Pres...

Страница 3: ...be left with the end user The manufacturer is not liable for costs or damages incurred by the user or third parties through the use of the device misuse or malfunction of the connection malfunction of...

Страница 4: ...mization of the inherent energy demand with PV facilities calculating the usage or feeding charge with tariff switching the ETS application also provides various monitoring functions In case of exceed...

Страница 5: ...4 Units 70 0 x 89 6 x 62 9 mm L x W x H UL94 V0 General Certification Applicable standards for CE marking EIB KNX certificated Tested for safety in accordance with DIN EN 61010 1 Tested for EMC compli...

Страница 6: ...ement ranges 0 10 10 100 THD U Harmonics U Measurement ranges 0 10 10 100 Typical measurement deviations per channel 10 or 0 1W 5 1 Typical measurement deviations 5 or 0 5mA 2 1 Typical measurement de...

Страница 7: ...are to measure at one single phase then this phase has to be connected to all three channels V1 V2 and V3 The supply for the voltage inputs may be made from any location downstream the main fuse since...

Страница 8: ...on Hereby no safety distances to the vicinity are required Since the current sensors are calibrated for each current channel it must be ensured that the accompanying current sensors are connected to t...

Страница 9: ...sible in a case of an extension the following is recommended Only use shielded lines with at least 0 5mm The shield of the extension must be connected to the shield wire drain wire of the existing mea...

Страница 10: ...n the web server of Enertex EibPC over the last 30 hours Figure 3 Example of the visualization of energy consumption Furthermore it is shown in this example how the progress of the three phase active...

Страница 11: ...ER LED lights up permanently after a short start up procedure about 3 seconds From that time the device performs measurements permanently If not already done the SD card for recording the measurement...

Страница 12: ...re released in the settings Otherwise the default values can be adopted With the default settings for the SD card recording all measured values except the harmonics are recorded on the SD card With a...

Страница 13: ...er this goes hand in hand that the measured values can be tracked by the bus with less accuracy Here a appropriate compromise depending on the fluctuation of the consumption loads should be found betw...

Страница 14: ...ore resetting is enabled Figure 9 Settings Intermediate counter 1 Example 1 With this configuration the intermediate counter sums up the three phase energy consumption each about 15 minutes and transm...

Страница 15: ...he energy costs in cent Finally a tariff must still be specified to calculate the costs Thereby Tariff 1 is released in the tab Tariff Then the parametrization of tariff 1 is done in tab Tariff 1 Figu...

Страница 16: ...ed for example over the last 6 months on a chart In addition the progress of the energy fed by PV the progress of the energy provided by the network and the balance of both are to be visualized over t...

Страница 17: ...three phase values the limit value of the three phase active power for load management is parametrized In principle the concept of load control is to work as follows If currently more energy is genera...

Страница 18: ...ve power limit message ID 66 are needed for switching on off a consumer load So the switching group object of the switching actuator of a consumer load has to be linked to the group object Active powe...

Страница 19: ...Energy counter three phase and Tariff cost counter three phase no settings have to be made Here the default values are used In the tab Intermediate counter 1 the energy counter is configured to count...

Страница 20: ...nfigured for the balanced energy Figure 19 Settings Intermediate counter 3 Example 2 In contrast to the Active energy counter consumption and Active energy counter generation the Active energy counter...

Страница 21: ...will be specified ct kWh in a later time Therefore Tariff cost counter generation tariff 2 is selected for the counter value Figure 21 Settings Intermediate counter 5 Example 2 As already mentioned t...

Страница 22: ...gative sign Figure 23 Settings Tariff 2 Example 2 Generally also the feed in rate is not depending on the time of day Therefore the tariff switching is deactivated by selecting of always active The pa...

Страница 23: ...arent power is the value resulting from active and reactive power This is always positive With the apparent power the utilization of resources such as cables or transformers can be assessed Power Fact...

Страница 24: ...t of the consumption counter In this counter only the consumed energy i e the energy flow in positive direction of the power count arrow is counted The value represents the consumed energy and is alwa...

Страница 25: ...d counter readings can be transmitted on the bus after a change The function is used for a complete representation of a measurement on the bus or in a diagram Since the measured values are only transm...

Страница 26: ...erent scenarios are possible Scenario Consumer counter Generation counter Consequence More energy is consumed than generated in the house counting not counting Energy is charged by the supply rate of...

Страница 27: ...count interval This value can then be used to show the energy consumption over one day The intermediate counter additionally offers the option to set a count interval with a trigger Thus it can be us...

Страница 28: ...quired It is also possible to parametrize two or three tariffs as always active Then the current delivery costs can be counted in tariff counter of tariff 1 and the compensation of a PV system can be...

Страница 29: ...Energy counter current value is reset at the end of the counting interval and then again starts to count Within the counting interval therefore only the counter of the group object Energy counter curr...

Страница 30: ..._Chx bzw P_3ph Q_3ph for three phase values Power factor Averaged measured value over the interval Pf_Chx Unbalanced load Averaged measured value over the interval Percentage represents the current of...

Страница 31: ...used Then the file must be saved using a simple text editor such as Editor or Wordpad The time to be set in the form of the time stamp which is also used in the recording files must now be entered in...

Страница 32: ...termediate counter are delayed for this time Thus the device can be configured so that transmission of counts of the counter do not overload the bus Request time and date after bus voltage recovery Ye...

Страница 33: ...from the voltage of channel 1 Transmit frequency cyclically x10s 0 1 2 17280 0 not transmit cyclically The group object with the measured frequency is transmitted cyclically at intervals of the param...

Страница 34: ...Request power values 0 1 0 or 1 The transmission of the measured values are requested with a group object which has the value parametrized here When requesting all measured values for active power re...

Страница 35: ...s with the measured values for active reactive apparent power and voltage of the channel 1 2 or 3 are transmitted cyclically at intervals of the parametrized value Transmit active power cyclically Yes...

Страница 36: ...d value of the active power of channel 1 2 or 3 a group object is transmitted Release of the limit parameters and the group object See also section Message of limit values Adopt limit value from bus f...

Страница 37: ...ssage at transient voltage peak Yes No In case of an appearance of a transient voltage spike with a peak value min 650V a group object is transmitted Release of the group object Transient voltages ope...

Страница 38: ...e of the limit parameter and the group object Limit value x0 1 0 1 2 1000 Limit value of the current on channel 1 2 or 3 which shall be monitored The limit is given here as a percentage of the referen...

Страница 39: ...e measured value for the above mentioned cycle time is transmitted Transmit unbalanced load cyclically Yes No It is set whether the measured value for the above mentioned cycle time is transmitted Tra...

Страница 40: ...egative limits it should be noted that the value 1 is transmitted when the measured value exceeds the limit as an absolute value Similarly the value 0 is transmitted when the measured value drops belo...

Страница 41: ...phase reference power 3 x 230 V x reference current If the threshold is selected to be negative then also the value for the hysteresis has to be selected by definition as negative Message at limit val...

Страница 42: ...ase tariff counter 1 Yes No The group objects and the parameters for tariff cost counter tariff 1 balance tariff cost counter tariff 1 consumption tariff cost counter tariff 1 generation are hereby re...

Страница 43: ...nd change are hereby released Transmit counter values at change in of current measured value 0 1 255 0 no transmission at change The group objects for the below mentioned counter values are transmitte...

Страница 44: ...et whether the counter value of the above mentioned cycle time is transmitted Transmit reactive energy counter cyclically Yes No It is set whether the counter value of the above mentioned cycle time i...

Страница 45: ...s for cyclical transmission are hereby released Transmit cyclically x10s tariff cost counter 0 to 172800 0 not transmit cyclically The group objects with the values of the balancing tariff cost counte...

Страница 46: ...measured value for the above mentioned cycle time is transmitted Transmit cyclically tariff cost counter 3 generation Yes No It is set whether the measured value for the above mentioned cycle time is...

Страница 47: ...gy counter consumption three phase Active energy counter generation three phase Tariff cost counter balance tariff 1 Tariff cost counter consumption tariff 1 Tariff cost counter generation tariff 1 Ta...

Страница 48: ...counter value before resetting Yes No After updating the group object previous value at a count interval limit this group object is transmitted automatically on the bus The message is delayed in acco...

Страница 49: ...for the tariff 2 can be parametrized Release tariff 3 Yes No The release of the parameters and group objects for the tariff 3 can be parametrized Tariff after bus voltage recovery no tariff Tariff 1 T...

Страница 50: ...rs time or trigger objects or always be active If by trigger object is selected then the two group objects are enabled With the value always active no tariff switching takes place See section Tariff C...

Страница 51: ...function Length Type Flags 2 General Request time 1 Bit 1 002 DPT_Bool C T The time of the Smartmeter can be requested by an other bus participant from the Smartmeter using this group object ID Name...

Страница 52: ...e limit of the voltage of channel 1 has been exceeded or fallen below ID Name Object function L nge Typ Flags 13 Measurement Ch1 Voltage failure message 1 Bit 1 002 DPT_Bool C T Group object that is t...

Страница 53: ...the channel1 ID Name Object function Length Type Flags 23 Measurement Ch1 THD I 2 Byte 8 010 DPT_Percent_V16 CR T Group object with the most recently determined THD I of the channel1 ID Name Object fu...

Страница 54: ...2 exceeds or falls below 60Vrms ID Name Object function Length Type Flags 33 Measurement Ch2 Voltage peak message 1 Bit 1 002 DPT_Bool C T Group object that transmits the value 1 if at channel 2 a tr...

Страница 55: ...the harmonics of the voltage of the channel 2 Explanation see section Measurement quantities ID Name Object function Length Type Flags 44 Measurement Ch2 Spectrum I 14 Byte New dpt Type have not been...

Страница 56: ...ol C T Group object that is transmitted with the value 1 or 0 if the limit of the current of channel 3 has been exceeded or fallen below ID Name Object function Length Type Flags 54 Measurement Ch3 Cu...

Страница 57: ...ent of the channel 3 Explanation see section Measurement quantities ID Name Object function Length Type Flags 64 Measurement three phase Active power 4 Byte 14 056 DPT_Value_Power CR T Group object wi...

Страница 58: ...ase Zero current limit message 1 Bit 1 002 DPT_Bool C T Group object that is transmitted with the value 1 or 0 if the limit of the zero current has been exceeded or fallen below ID Name Object functio...

Страница 59: ...r con 4 Byte 13 010 DPT_ActiveEnergy CR T Counter value of the active energy counter consumption of channel 3 This counter value is always positive or 0 ID Name Object function Length Type Flags 85 En...

Страница 60: ...ate of tariff 1 The costs are always positive or 0 ID Name Object function Length Type Flags 94 Tariff counter 1 three phase values Tariff cost counter gen 4 Byte 13 001 DPT_Value_4_Cou nt CR T The ob...

Страница 61: ...3 and from the rate of tariff 3 The costs are always positive or 0 ID Name Object function Length Type Flags 102 Tariff counter 3 three phase values Tariff cost counter gen 4 Byte 13 001 DPT_Value_4_C...

Страница 62: ...us is permanent ID Name Object function Length Type Flags 110 Intermediate counter 1 External cost counter limit 4 Byte 13 001 DPT_Value_4_Cou nt CR T When writing to this object the limit is adopted...

Страница 63: ...us is permanent ID Name Object function Length Type Flags 118 Intermediate counter 2 External cost counter limit 4 Byte 13 001 DPT_Value_4_Cou nt CR T When writing to this object the limit is adopted...

Страница 64: ...us is permanent ID Name Object function Length Type Flags 126 Intermediate counter 3 External cost counter limit 4 Byte 13 001 DPT_Value_4_Cou nt CR T When writing to this object the limit is adopted...

Страница 65: ...us is permanent ID Name Object function Length Type Flags 134 Intermediate counter 4 External cost counter limit 4 Byte 13 001 DPT_Value_4_Cou nt CR T When writing to this object the limit is adopted...

Страница 66: ...us is permanent ID Name Object function Length Type Flags 142 Intermediate counter 5 External cost counter limit 4 Byte 13 001 DPT_Value_4_Cou nt CR T When writing to this object the limit is adopted...

Страница 67: ...on Length Type Flags 150 Intermediate counter 6 External cost counter limit 4 Byte 13 001 DPT_Value_4_Cou nt CR T When writing to this object the limit is adopted from the bus If the parameter Adopt l...

Страница 68: ...If in contrast the parameter is set on permanent then the rate adopted from the bus is permanent ID Name Object function Length Type Flags 159 Tariff 3 Trigger Tariff start 1 Bit 1 017 DPT_Trigger C...

Страница 69: ...terrupting the power supply it is alternatively possible to reboot the application The device will now perform the firmware update during startup sequence During the copying procedure the POWER SD WRI...

Отзывы: