Handbuch-KnxSmartmeter-85A-en-3.odt, 2018-10-04
Seite 65 von 69
ID
Name
Object function
Length
Type
Flags
130 Intermediate
counter 4
Cost counter-current value
4 Byte
[13.001]
DPT_Value_4_Cou
nt
CR-T-
This object contains the current cost counter value of the intermediate counter in ct. The counter value may be
positive or negative. The value of the group object is respectively copied after the lapse of the counting interval into
the group object “Cost counter - previous value” and then reset.
ID
Name
Object function
Length
Type
Flags
131 Intermediate
counter 4
Cost counter-previous value.
4 Byte
[[13.001]
DPT_Value_4_Cou
nt
CR-T-
The object contains the cost counter value from the previous count interval of the intermediate counter in ct. If
configured, this value is transmitted on the bus after its update. When transmitting the parameter “General - Offset
when transmitting of intermediate counter values in (s)” operates as a transmission delay.
ID
Name
Object function
Length
Type
Flags
132 Intermediate
counter 4
Limit message
1-Bit
[1.002]
DPT_Bool
C--T-
Group object that transmits the value 1 or 0, if the limit of the intermediate counter has been exceeded or fallen
below.
ID
Name
Object function
Length
Type
Flags
133 Intermediate
counter 4
External energy counter limit
4 Byte
[13.010]
DPT_ActiveEnergy
CR-T-
When writing to this object the limit is adopted from the bus. If the parameter “Adopt limit value from the bus” is set on
“flighty” then the value adopted by the bus is discarded after the next reset of the intermediate counter. If in contrast
the parameter is set on “permanent” then the limit adopted by the bus is permanent.
ID
Name
Object function
Length
Type
Flags
134 Intermediate
counter 4
External cost counter limit
4 Byte
[13.001]
DPT_Value_4_Cou
nt
CR-T-
When writing to this object the limit is adopted from the bus. If the parameter “Adopt limit value from the bus” is set on
“flighty” then the value adopted by the bus is discarded after the next reset of the intermediate counter. If in contrast
the parameter is set on “permanent” then the limit adopted by the bus is permanent.
ID
Name
Object function
Length
Type
Flags
135 Intermediate
counter 4
Reset counter value
1-Bit
[1.017]
DPT_Trigger
C-W--
If the value 1 is transmitted to this object, then the intermediate counter behaves as it reaches a time interval
boundary. The group object is released by the parameter selection “Count interval - by trigger object”. See also
section Intermediate Counter.
ID
Name
Object function
Length
Type
Flags
136 Intermediate
counter 5
Energy counter-current value
4 Byte
[13.010]
DPT_ActiveEnergy
CR-T-
The object contains the current energy counter value of the intermediate counter in Wh. The counter value can be
positive or negative. The value of the group object is respectively copied after the lapse of the counting interval into
the group object “Energy counter - previous value” and then reset.
ID
Name
Object function
Length
Type
Flags
137 Intermediate
counter 5
Energy counter-previous value.
4 Byte
[13.010]
DPT_ActiveEnergy
CR-T-
The object contains the energy counter value from the previous count interval of the intermediate counter in Wh. If
configured, this value is transmitted on the bus after its update. When transmitting the parameter “General - Offset
when transmitting of intermediate counter values in (s)” operates as a transmission delay.
Enertex
®
Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - Deutschland - [email protected]