7
IOM, ZS/ZT Models
Enertech Global
where the ambient temperature will remain
above 55°F and should be located in a way
that piping and ductwork or other permanently
installed fixtures do not have to be removed for
servicing.
Pre-Installation Steps:
1. Compare the electrical data on the unit
nameplate with packing slip and ordering
information to verify that the correct unit
has been shipped.
2. Remove any packaging used to support or
hold the blower during shipping.
3. Inspect all electrical connections
and wires. Connections must be clean and
tight at the terminals, and wires should not
touch any sharp edges or copper pipe.
4. Verify that all refrigerant tubing is free of
dents and kinks. Refrigerant tubing should
not be touching other unit components.
5. Before unit start-up, read all manuals and
become familiar with unit components
and operation. Thoroughly check the unit
before operating.
⚠
CAUTION
⚠
ALL GEOTHERMAL EQUIPMENT IS DESIGNED FOR
INDOOR INSTALLATION ONLY. DO NOT INSTALL
OR STORE UNIT IN A CORROSIVE ENVIRONMENT
OR IN A LOCATION WHERE TEMPERATURE AND
HUMIDITY ARE SUBJECT TO EXTREMES. EQUIPMENT
IS NOT CERTIFIED FOR OUTDOOR APPLICATIONS.
SUCH INSTALLATION WILL VOID ALL WARRANTIES.
⚠
WARNING
⚠
FAILURE TO FOLLOW THIS CAUTION MAY RESULT
IN PERSONAL INJURY. USE CARE AND WEAR
APPROPRIATE PROTECTIVE CLOTHING, SAFETY
GLASSES AND PROTECTIVE GLOVES WHEN
SERVICING UNIT AND HANDLING PARTS.
⚠
CAUTION
⚠
BEFORE DRILLING OR DRIVING ANY SCREWS INTO
CABINET, CHECK TO BE SURE THE SCREW WILL NOT
HIT ANY INTERNAL PARTS OR REFRIGERANT LINES.
SECTION 2: INSTALLATION INTRODUCTION
Components:
Master Contactor: Energizes Compressor and
optional Hydronic Pump and/or Hot Water
Generator (HWG) package.
Logic Board: Logic Board operates the
compressor and protects unit by locking out
when safety switches are engaged. It also
provides fault indicator(s).
Terminal Strip: Provides connection to the
thermostat or other accessories to the low
voltage circuit.
Transformer: Converts incoming (source)
voltage to 24V AC.
Low Voltage Breaker: Attached directly to
transformer, protects the transformer and low
voltage circuit.
Reversing Valve: Controls the cycle of the
refrigerant system (heating or cooling).
Energized in cooling mode.
High Pressure Switch: Protects the refrigerant
system from high refrigerant pressure, by locking
unit out if pressure exceeds setting.
Low Pressure Switch: Protects the refrigerant
system from low suction pressure, if suction
pressure falls below setting.
Flow Switch (Freeze Protection Device): Protects
the water heat exchanger from freezing,
by shutting down compressor if water flow
decreases.
Electric Heater (External Mount): Provides
auxiliary heat during cold temperatures and
provides electric backup if unit malfunctions.
Blower Motor (ECM): ECM (Electronically
Commutated Motor) for variable fan speeds.
Compressor (Copeland Scroll): Pumps
refrigerant through the heat exchangers and
pressurizes the refrigerant, which increases the
temperature of the refrigerant.
Содержание ZS.
Страница 24: ...24 Enertech Global IOM ZS ZT Models Unit Electrical Data ZS 018 042 ECM Models SECTION 4 UNIT DATA INFORMATION...
Страница 25: ...25 IOM ZS ZT Models Enertech Global Unit Electrical Data ZS 048 072 ECM Models SECTION 4 UNIT DATA INFORMATION...
Страница 26: ...26 Enertech Global IOM ZS ZT Models Unit Electrical Data ZS 018 042 PSC Models SECTION 4 UNIT DATA INFORMATION...
Страница 27: ...27 IOM ZS ZT Models Enertech Global Unit Electrical Data ZS 048 072 PSC Models SECTION 4 UNIT DATA INFORMATION...