22
Enertech Global
IOM, ZS/ZT Models
PSC Fan Performance/Dip Switch Settings- Single-Stage Compressor Units
SECTION 4: UNIT DATA INFORMATION
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.60
0.70
0.80
H
1050 1045 1040 1040 1035 1030 1025 1015 1000
965
925
875
M
600 (018)
690
685
675
665
650
645
635
620
600
575
525
460
L
600
590
580
570
555
535
515
510
500
445
410
380
H
1000 (030)
1110 1125 1135 1140 1140 1140 1140 1135 1130 1110 1090 1055
M
750 (024)
780
780
780
785
785
785
780
775
770
750
700
660
L
660
655
650
650
645
640
635
620
600
585
570
510
H
1100
1210 1215 1220 1215 1210 1205 1195 1195 1190 1165 1135 1100
M
865
870
870
875
875
875
870
865
860
845
825
790
L
685
700
710
710
710
705
700
700
695
670
630
595
H
1400
1620 1620 1615 1610 1605 1600 1595 1580 1565 1520 1465 1405
M
1000 1100 1015 1018 1020 1023 1025 1028 1030 1040 1025
990
L
850
860
865
870
875
875
875
873
870
860
850
820
H
2090 2070 2050 2035 2015 1990 1965 1940 1910 1855 1790 1710
M
1500
1740 1745 1750 1740 1730 1720 1710 1695 1675 1645 1600 1535
L
1400 1410 1420 1430 1435 1440 1440 1440 1440 1420 1390 1330
H
2200 (072)
2560 2540 2515 2505 2495 2470 2445 2420 2390 2350 2290 2210
M
1900 (060)
2000 2000 1995 1998 2000 2005 2010 2005 1995 1940 1935 1885
L
1590 1605 1620 1630 1640 1645 1645 1645 1645 1640 1625 1600
Notes:
High
Med
Low
X
0.7
X
0.8
X
0.7
X
0.8
X
0.8
X
0.8
X
0.9
X
0.8
X
X
X
0.9
X
0.7
X
0.8
X
0.9
X
X
X
0.9
X
X
0.9
X
X
X
1.0
X
X
0.9
X
1.1
AXCH101MB
AXCH101MB
AXCH151MB
AXCH101LB
AXCH151LB
1. PSC Blower motors come with 3 or 4 speed taps. To change the speed of the motor to a higher or lower speed, remove the electric box cover that is
mounted on the blower. Locate the label on the motor to identify the wire color for each speed. Remove the wire nut on the existing speed and
replace with the wire of selected speed.
2. Max ESP and speed settings for ZS models with external electric heat is shown below. Exceeding the Max ESP may result in nuisance trips of the electric heat. Thermal limits are rated
at 100,000 cycles.
Model
Electric Heater
Speed
Max
Static
*ZS Series‐Electric Heat Limitations
AXCH051MB
018
024/030
060/072
036
042
048
10 x 8
3/4
060/072
11 x 10
1
AXCH051MB
AXCH101MB
AXCH051MB
AXCH101MB
AXCH051MB
048
042
10 x 8
1/2
10 x 8T
1/3
036
10 x 8
1/3
018
10 x 8T
1/4
024/030
*ZS Series PSC Fan Performance Data
Model
Motor
Speed
1
Blower
Size
Motor
HP
CFM Nominal
Static Pressure (inches w.c.)
Содержание ZS.
Страница 24: ...24 Enertech Global IOM ZS ZT Models Unit Electrical Data ZS 018 042 ECM Models SECTION 4 UNIT DATA INFORMATION...
Страница 25: ...25 IOM ZS ZT Models Enertech Global Unit Electrical Data ZS 048 072 ECM Models SECTION 4 UNIT DATA INFORMATION...
Страница 26: ...26 Enertech Global IOM ZS ZT Models Unit Electrical Data ZS 018 042 PSC Models SECTION 4 UNIT DATA INFORMATION...
Страница 27: ...27 IOM ZS ZT Models Enertech Global Unit Electrical Data ZS 048 072 PSC Models SECTION 4 UNIT DATA INFORMATION...