SECTION 8: SOFT START CONTROLS
8
Specifications are subject to change without notice (03.09.2014)
RSBS2332A2V22C24SM28, RSBS2325A2V22C17SM29
Mode of Operation (Voltage Dips)
Mains operational voltage
M
Ue: 230VAC
U
>= 200ms
0VAC
0
Green LED
G
Control Voltage
C
200ms
Controller output
C
Alarm indication, Red LED
A
Alarm relay contact
A
Alarm recovery
Flashing
On
140VAC < Ue < 160VAC
9
Mains operational voltage
U
Ue: 230VAC
>
0VAC
Green LED
C
Control Voltage
2
100ms
C
Controller output
A
Alarm indication, Red LED
A
Alarm relay contact
Alarm recovery
>
Flashing
On
>=100ms
O
90VAC < Ue < 140VAC
Note:
1. When a voltage dip and/or interruption is detected the Under voltage alarm will be triggered (2 flashes on red LED).
2. If, during bypass, the current (Ie) is <=2.5AACrms for Ue>=180VAC, the under-voltage alarm will also be triggered as this might indicate a voltage interruption
condition.
3. Voltage dips/interruptions occurring during recovery between starts and/or alarm recovery shall be ignored.
4. Voltage dips/interruptions are not monitored during ramping and idle (control OFF) states.
Mode of Operation (Voltage Interuptions)
Содержание ZS.
Страница 24: ...24 Enertech Global IOM ZS ZT Models Unit Electrical Data ZS 018 042 ECM Models SECTION 4 UNIT DATA INFORMATION...
Страница 25: ...25 IOM ZS ZT Models Enertech Global Unit Electrical Data ZS 048 072 ECM Models SECTION 4 UNIT DATA INFORMATION...
Страница 26: ...26 Enertech Global IOM ZS ZT Models Unit Electrical Data ZS 018 042 PSC Models SECTION 4 UNIT DATA INFORMATION...
Страница 27: ...27 IOM ZS ZT Models Enertech Global Unit Electrical Data ZS 048 072 PSC Models SECTION 4 UNIT DATA INFORMATION...