23
IOM, ZS/ZT Models
Enertech Global
Unit Electrical Data, ZT 024 - 072, ECM Models
When any compressor bearing unit is connected to a weak power supply, starting current will generate a significant “sag” in the voltage
which reduces the starting torque of the compressor motor and increases the start time. This will influence the rest of the electrical system in
the building by lowering the voltage to the lights. This momentary low voltage causes “light dimming”. The total electrical system should be
evaluated with an electrician and HVAC technician. The evaluation should include all connections, sizes of wires, and size of the distribution
panel between the unit and the utility’s connection. The transformer connection and sizing should be evaluated by the electric utility provider.
NOTE: Proper Power Supply Evaluation
SECTION 4: UNIT DATA INFORMATION