background image

4

or may not be billed for Off-Peak demand. On-Peak times 
vary from utility to utility; as well as, by season.

To  benefi t  from your Energy  Sentry 9312 Demand 

Management System you must have a demand measuring 
electric meter equipped with the TOU/Demand option and 
be billed on a TOU Demand Rate from your utility. Obtain 
a rate booklet or rate sheet from your utility company that 
describes your electric rate, the KW charges, On-Peak and 
Off-Peak hours, and how to read your electric meter. We 
recommend that you read your metered demand on the day 
prior to when the meter is read by the power company, to 
verify that your setting matches the meter’s reading.

Where the 9312 
Technology Comes In

You wouldn’t need a 9312 to take advantage of TOU 

Demand  Rates if you could go through your home and 
continuously turn off heating or cooling circuits and major 
appliances to level out peak demand whenever necessary. 
But remember,  one slip in any one demand interval and 
your utility bill would refl ect a high demand charge.

The 9312 takes over this diffi cult, continuous burden 

for you. The 9312 is one of the most sophisticated products 
available for controlling peak demand. When properly 
used, it can result in average monthly savings of up to 35% 
and as much as 50%  during heavy-use months. The sole 
purpose of the 9312 is to effi ciently allocate the usage of 
electricity to electrical loads so that demand peaks are kept 
below the level which you have set.

How the 9312 Works

The 9312 contains a microcomputer which turns 

certain circuits off when necessary to keep your home’s 
peak demand below a limit that you preset. Not all circuits 
need to be controlled by the 9312. Circuits controlled 
usually include the air conditioning, all heating zones, 
the dryer, the water heater, or any other load with some 
thermal storage capacity or “thermal inertia”.

In a typical all-electric home, the winter morning 

routine may involve turning up some thermostats, operat-
ing the range, water heater and other appliances. Normally, 
operation of these loads causes a morning peak (such as 
that illustrated in Figure 1) which registers on the demand 
meter. In the summer, a typical routine might include the 
water heater cycling on and off as needed, operating the 
range and later in the morning or early afternoon running 
the air conditioner or cooling systems in your home. In 
this case, these loads might cause an afternoon or evening 
peak. In both cases, the peak demand used by your home 
is caused by your use of electricity due to the season or 
weather; as well as other normal non-weather related uses 
of electricity.

Now, let’s put the 9312 to work. The start time of the 

On-Peak period has just passed. The 9312 measures the 
amount of power being used by the home as you go about 
your daily business and it recognizes when the demand 
limit is about to be exceeded. It waits a few minutes to see 

if these loads are going to turn off by themselves while it 
carefully calculates the average demand of the home. If 
the power consumption continues to exceed the demand 
limit, it begins to turn off loads. It turns off the least impor-
tant load fi rst, using the load control strategy that you set. 
As the power consumption drops, it then allows the most 
important loads to come back on fi rst. There are several 
optional load control strategies. A typical strategy might 
provide power to a higher priority load such as the dryer 
and cut back on the heating or cooling loads in one or more 
rooms, or the water heater while the higher priority load is 
on. When the dryer turns off, the power it had been using is 
channeled back to the room heating or cooling, thus main-
taining comfort but reducing peak demand. The end result 
is that while you have still used about the same amount of 
energy normally called upon by your lifestyle, this usage 
has been leveled out to reduce the On-Peak demand. This 
is illustrated by Owner B in Figure 1.

How the 9312 Saves

Now that we’ve examined how the 9312 enables 

you to use the energy you are accustomed to, but spreads 
this usage out by turning off non-critical loads for short 
periods of time, let’s look at how this saves you money. 
Remember, the utility company helps you save by offering 
the TOU Demand Rate which is a lower rate per unit of 
total energy consumed (Kwh). You can save money under 
this rate if you control your peak energy usage to keep the 
corresponding demand charge low.

The following hypothetical examples illustrate how 

the  Energy  Sentry 9312 helps you save. Three cases are 
presented for a single residence. In all three cases the total 
energy consumption is the same. The differences are in the 
utility rate structure and whether or not an Energy Sentry 
9312 is installed.

Case I

 is an all-electric home billed under the Energy 

Rate. This differs from the Demand Rate, in that there is 
a higher charge for total energy used and no charge for 
demand. Most homes not under the TOU  Demand  Rate 
are billed under the Energy Rate. Table 1 on the next page 
shows a monthly energy use of 3000 Kwh. Although rates 
vary from utility to utility, the electric bill  based on an 
actual utility rate sheet for this energy usage level would 
be $218.28.*

Case II

  is  the same all-electric home billed under 

the TOU Demand Rate. This rate is structured such that 
11:00 AM to 10:00 PM Monday through Friday is the 
On-Peak time during the summer schedule. The remain-
ing 13 hours from 10:00 PM to 11:00 AM and weekends 
are the Off-Peak time when customers are not billed for 
Off-Peak demand. For example, let’s assume that the 
energy usage remains at 3000 Kwh for the billing period 
and that 750 Kwh were used in the On-Peak times and the 
remaining 2250 Kwh were used during Off-Peak times. 
In this case, peak energy usage plays an important part in 
determining the total bill. Although energy use peaks will 
vary from month-to-month, a typical value for a high-use 
month might be 19 KW.  Based on a total usage of 3000 
Kwh, the electric bill based on actual utility rates would 
be $201.54**. Compared to Case I (the standard Energy 
Rate), use of the TOU Demand Rate results in savings of 
approximately 8% for the same energy usage. The  demand 
charge for the high peak demand during the On-Peak time 

Содержание 9312

Страница 1: ...Computerized Energy Management Model 9312 Owner s Installation Manual Helping you to use energy more efficiently ...

Страница 2: ...ools Materials Required 17 3 0 Pre Installation System Check List 17 4 0 Locating C D Unit 18 5 0 Locating and Mounting Relay Unit 18 6 0 Running Control Cable 19 7 0 Wiring Control Cable to C D Unit 19 8 0 Mounting C D Unit 20 9 0 Wiring Control Cable to Relay Unit 20 10 0 Wiring 120 VAC Power Supply to Relay Unit 21 11 0 Installing Wiring Current Transformers 21 12 0 Creating a Load Schedule Mak...

Страница 3: ...FCC Rules which are designed to provide reasonable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interferen...

Страница 4: ...de key until the left display reads dL This is your demand limit Simultaneously press the Demand Limit and Increase keys and raise the system s demand limit by 0 5 KW Wait one or two hours to give your home a chance to heat or cool If the change you just made does not feel sufficient after that time press the Demand Limit and Increase key to increase the system s demand limit another 0 5 KW Repeat...

Страница 5: ...e is illustrated by the largest spike in Owner A in Figure 1 Under the TOU Demand Rate you pay for both total energy used in Kwh like the Energy Rate and for your peak demand during the On Peak time over the billing period highest average KW demand see page 12 for definition In addition utilities offer reduced or no KW demand charges during the Off Peak times When compared to the Energy Rate the T...

Страница 6: ...ower consumption continues to exceed the demand limit it begins to turn off loads It turns off the least impor tant load first using the load control strategy that you set As the power consumption drops it then allows the most important loads to come back on first There are several optional load control strategies A typical strategy might provide power to a higher priority load such as the dryer a...

Страница 7: ...ak and Off Peak hours the proportion of energy consumed during On Peak and Off Peak times and the demand limit Superior Features of the 9312 Real Time Control The 9312 contains a real time clock which allows the demand management system to take advantage of TOU Demand Rates available from some utilities and modify the control strategy accordingly This feature enhances the money savings and comfort...

Страница 8: ...components the Control Display Unit Relay Unit s and the Current Transform ers The System Diagram in Figure 3 in the Installation Manual shows how these components are connected to control loads at the circuit breaker panel Your 9312 con trols only those loads which are connected to it However the total demand from all household loads are measured continuously These loads will vary depending on ap...

Страница 9: ...rned on when all controlled loads have been turned off by the 9312 but demand is still approaching the demand limit When this occurs you must either reduce the uncon trolled demand or increase the demand limit as suggested in the operating instructions Circuit On Indicators 6 These indicators when lit tell you which control points are enabled A Circuit On indication does not necessarily mean that ...

Страница 10: ...ce will vary with the uniqueness of each house its occupants energy use and the utility s averaging period To arrive at the best demand setting for you requires some trial and error see Table 2 The 9312 has a demand limit setting range of 2 0 to 49 5 KW in 5 KW increments A good starting demand limit is 5 KW If you need more energy to maintain comfort increase the KW level by only 5 KW If after an...

Страница 11: ...ning of each 1 minute interval This way Off Time of rotating loads is minimized The rotate strategy is particularly useful where equal priority rotation may serve several heating loads minimiz ing the Off Time of each load during rotation Thus the reduction in demand is shared by several loads and the 1 Press and hold Alarm Volume key 11 2 Simultaneously press the Decrease key 7 or the Increase ke...

Страница 12: ...larly attractive feature because heat pump and air conditioning compressors requiring time delay switching may be controlled under a strategy to best fit your application lifestyle or use pattern The load shedding priority selected is based on the type of heating and cooling equipment and the design of your house If desired the priorities may be easily changed Priority 17 The 9312 allows the use o...

Страница 13: ...ontrolling demand and it will increase the comfort level of your home Shifting use of all loads possible to Off Peak times will help to reduce your On Peak energy usage charge and increase your savings In most TOU Demand Rates the On Peak demand and energy charges are substantially more costly than the Off Peak charges Consult your utility to determine your On and Off Peak times Service of Heating...

Страница 14: ... remains the same regardless of the number of Kwh s used Also called Flat Rate Under this rate demand is not measured recorded or billed Instantaneous Demand The electricity in kilowatts currently being drawn by the electrical service of a build ing at any instant in time Kilowatt KW 1 000 watts Kilowatt Hour Kwh The basic measurement of electric energy consumption as metered by the electric utili...

Страница 15: ... d1 is displayed Release keys Temperature dE The current temperature in dE grees Fahrenheit inside the 9312 s C D Unit Day of Week do The current day of the week 1 Sunday 2 Monday 3 Tuesday 4 Wednesday 5 Thursday 6 Friday 7 Saturday Date Month Day dA The current month and day of the month Setting range from 1 1 to 12 31 Year Yr The current year Auto Daylight Saving Adjust dS Allows the 9312 to be ...

Страница 16: ...g tells the 9312 how many relays are installed starting from Control Point 1 and counting up to 16 This setting turns off unused control points The number programmed into this setting should be equal to the number of relays and all relays should be on consecutive control points starting with 1 Only control points enabled at this setting will appear in subsequent settings for priorities Minimum On ...

Страница 17: ... Start Time 12 00 a m 11 59 p m F2 Fall 1 End Time 12 00 a m 11 59 p m F3 Fall 2 Start Time 12 00 a m 11 59 p m F4 Fall 2 End Time 12 00 a m 11 59 p m Fd Fall Start Date 0 0 12 31 SS Saturday Sunday On Off Peak on oFF H1 Holiday 1 0 0 12 31 H2 Holiday 2 0 0 12 31 H3 Holiday 3 0 0 12 31 H4 Holiday 4 0 0 12 31 H5 Holiday 5 President s Day 0 0 12 31 oFFP onP H6 Holiday 6 Memorial Day 0 0 12 31 oFFP o...

Страница 18: ...n Peak Demand Limit Period 6 2 0 49 5 o6 Off Peak Demand Limit Period 6 2 0 49 5 oFF oFF2 oFF3 oFF4 oFF5 d7 Start Date Period 7 0 0 12 31 L7 On Peak Demand Limit Period 7 2 0 49 5 o7 Off Peak Demand Limit Period 7 2 0 49 5 oFF oFF2 oFF3 oFF4 oFF5 d8 Start Date Period 8 0 0 12 31 L8 On Peak Demand Limit Period 8 2 0 49 5 o8 Off Peak Demand Limit Period 8 2 0 49 5 oFF oFF2 oFF3 oFF4 oFF5 d9 Start Da...

Страница 19: ...stallation Manual 17 1 0 Introduction This manual contains instructions for the installation checkout and programming of the Energy Sentry 9312 Demand Management System In order to ensure proper installation and warranty coverage please read this manual thoroughly before proceeding with the installation Note All wiring must be installed in accordance with national and local electrical codes Import...

Страница 20: ...s C D Unit will only recess in the wall correctly between studs because of the unit s depth 4 4 Drill screw holes first with 1 8 drill 4 5 Cut C D mounting hole with drywall knife being careful not to make it too large 4 6 Install the four C D Unit mounting clips P N 09000 02101 by pressing them onto the drywall in position over the mounting holes In most cases they should stay in place by themsel...

Страница 21: ...s 2 voltage compartment This com partment is found on the right side of the relay box Aseparate conduit may also be required for the control cable 0 375 diameter 5 2 3 If installing an Expansion Relay Unit follow the pro cedure in paragraph 5 2 2 5 2 4 Vacuum out all dry wall dust metal chips wood chips and other foreign objects which may affect operation of the system 6 0 Running Control Cable Af...

Страница 22: ...t the screw through the plastic housing through the hole in the short side of the C D Unit mounting clips through the drywall and into the small hole on the long side of the mounting clip The sheet metal screw will thread through the small hole and tighten the C D Unit enclosure to the wall Repeat this procedure with the other three screw s positions 8 4 When all four screws have been installed th...

Страница 23: ...ng lug on the left side of the relay plate 10 5 Repeat instructions 10 2 through 10 4 for an Expanded Relay Unit Both Relay Units MUST be phased the same Caution Leave circuit breaker off until installation is complete 11 0 Installing Wiring Current Transformers Caution Installation of Current Transformers may need to be coordinated with the local utility company 11 1 Disconnect main power to the ...

Страница 24: ...s with these types of heating systems the loads be connected as follows Example 1 Load Control Strategy Combination Circuit Load Priority 1 Dryer 1 2 Hot Water Heater 2 3 Heat 1 3 4 Heat 2 3 5 Heat 3 3 6 Heat 4 3 7 Heat 5 3 8 Heat 6 3 12 1 2 For Homes With Heat Pumps Without Compressor Connected Example Only In some heating climates it may be preferable not to connect the heat pump compressor to t...

Страница 25: ... a short length of 10 or 12 AWG wire depending on circuit breaker size which runs into the Relay Unit Wire nut this length of wire to one lead of the relay s contact With another short length of the appropriately sized wire wire nut it to the other lead of the relay s contact Connect that same wire back to the circuit breaker s terminal where the first wire was originally removed as shown in Figur...

Страница 26: ...ump com pressors to the Energy Sentry unit is normally accom plished by inserting a 3 Amp low voltage signal relay in series with the low voltage 24 VAC thermostat control loop as shown in Figure 10 Generalized Drawing This can be done in one of two ways 1 Use the low voltage relays on the Data Link PC Board for Circuits 2 and 3 or 2 Use remote low voltage relays Normally the relay is inserted in ...

Страница 27: ...stem Checkout 17 1 Prior to Test a Turn off ALL circuit breakers in the circuit breaker panel b Turn on thermostats switches for controlled loads 17 2 Initial Operation Test a Ensure all circuit breakers in the circuit breaker panel are off b Turn on the 9312 circuit breaker c Control Display Unit should turn on beep once and light up with id showing in the Mode display If the unit fails to light ...

Страница 28: ...nce all loads are shed the alarm will sound because the demand level is most likely still above the demand limit of 2 KW When this happens set the demand limit to its normal level apx 6 8 KW or whatever it may be for your specific home at that time of the year and the alarm should stop 17 6 Restore household loads to the desired condition The circuit breaker marked Energy Sentry or 9312 should be ...

Страница 29: ..._________________________ ______________ mins on ____ off ____ 15 ___________________________________ ______________ mins on ____ off ____ 16 ___________________________________ ______________ mins on ____ off ____ Control Points 2 and 3 are shipped with 8 minutes on and 5 minutes off See Appendix B page for instructions Owner 1 Record circuit assignments above and in the space provided on the key...

Страница 30: ...1 H2 7 4 Set Holiday Date 2 H3 12 25 Set Holiday Date 3 H4 0 0 Set Holiday Date 4 H5 onP Set Holiday Date 5 H6 onP Set Holiday Date 6 H7 onP Set Holiday Date 7 H8 onP Set Holiday Date 8 H9 onP Set Holiday Date 9 oP Reset Off Peak Peak Demand oL oFF Set Off Peak Demand Limit HL oFF Set High Instantaneous Limit nr 8 Set the Number of Relays Used Pr_1 1 Set Priority for Relay 1 Pr_2 2 Set Priority fo...

Страница 31: ... Demand Limit Period 2 o2 oFF Set Off Peak Demand Limit Period 2 d3 0 0 Set Start Date Period 3 L3 6 Set On Peak Demand Limit Period 3 o3 oFF Set Off Peak Demand Limit Period 3 d4 0 0 Set Start Date Period 4 L4 6 Set On Peak Demand Limit Period 4 o4 oFF Set Off Peak Demand Limit Period 4 d5 0 0 Set Start Date Period 5 L5 6 Set On Peak Demand Limit Period 5 o5 oFF Set Off Peak Demand Limit Period 5...

Страница 32: ...effect 4 Notification to BraydenAutomation Corporation or its authorized dealer under this warranty must be received within one week after discovering any defect in materials or workmanship 5 If the Energy Sentry Demand Management System is removed and returned to the authorized service dealer or Brayden Automation Corporation 6230 Aviation Circle Loveland CO 80538 for repair or replacement under ...

Страница 33: ...Brayden Automation Corp 6230 Aviation Circle Loveland CO 80538 970 461 9600 FAX 970 461 9605 www brayden com P N 09312 94100A ...

Отзывы: