8 Troubleshooting
TopCal S CPC 300
132
EHauser
8.7.2
Pneumatics and hydraulics CPG 300 non-Ex
8.8
Replacing the device fuses
#
Warning!
Danger to personnel.
Before replacing the fuse, make sure the device is voltage-free.
Fuse CPM 153:
•
Position of the fuse holder: "A" in fig. 36.
•
Use only a 5 x 20 mm fine-wire fuse with 3.15 mA, medium slow-blow. All other fuses
are not permitted.
Fuse CPG 300
•
Position of the fuse holder: "A" in fig. 39.
•
Use only a 5 x 20 mm fine-wire fuse with 3.15 mA, medium slow-blow. All other fuses
are not permitted.
Multihose:
Connection
Signal
MS1
free
MS2
Assembly in measuring position
MS3
Assembly in maintenance
position
MS4
free
MS5
"Measurement" feedback (n/a
with inductive feedback)
MS6
"Maintenance" feedback (n/a with
inductive feedback)
MS7
free
MS8
free
MS9
free
MS10 free
Valves (controlled electrically)
Name
Use
V3
Pump drive
V4
Revolver drive
V5
Assembly control
Pressure switch
Name
Use
S1
Compressed air monitoring
S2
Feedback
"Measurement" (not used with
inductive feedback)
S3
Feedback
"Maintenance" (not used with
inductive feedback)
S4
Conveyance pressure
monitoring
Fig. 42:
Pneumatics and hydraulics plans for CPG 300 non-Ex
Needle valves
N1
Preadjusted throttle for revolver
control time.
N2
Fine adjustment for pump
control time
Close the valve and open it ¼
revolution.
V5
V4
V3
S1
S2
S3
P1
MS5 MS6
MS2 MS3
V5 bottom
V5 top
V5
top / bottom
V4
top / bottom
V4
top
V4
N1
N2
bottom
C07-CPC300xx-04-12-00-en-009.EPS