WirelessHART Adapter SWA70
8 Configuration
Hauser
71
Linearization
If the
Special Curve
option is selected in the
Linearization Mode
parameter, you must make
additional settings in the
Linearization
window.
Comply with the following rules:
• You can enter between 2 and 32 value pairs.
• The X values must rise monotonically. The Y values must rise or fall monotonically. Red fields
indicate an error.
• The full scale values of the value range must correspond to those in the
4-20 mA
window
.
A graphic shows the linearization curve.
Parameter
Meaning
Example
X1 to X32
Input value X1 to X32 for linearization in mA
Y1 to Y32
Output values Y1 to Y32 for linearization in the selected unit for
the "Primary Variable Unit" parameter
Read
Press the button to read values from the WirelessHART Adapter
and transfer them to the linearization table.
Write
Press the button to write the values from the linearization table to
the WirelessHART Adapter.