Prosonic T - FMU 130, 131, 230, 231, 232
Hauser
Information on the Measuring Point
Diagnosis and Troubleshooting
Prosonic T distinguishes between the operating faults
alarm
and
warning
.
2-wire
If the Prosonic T Identifies an Alarm
• if the display is plugged in, the
bargraph flashes
• the current output adopts a
preselected value (–10% = 3.8 mA,
+110%, HOLD)
• an error code is output in V9H0
4-wire
If the Prosonic T Identifies an Alarm
• the red LED lights up
• if the display is plugged in, the
bargraph flashes
• the current output adopts a
preselected value (–10% = 2.4 mA,
+110%, HOLD)
• an error code is output in V9H0
If the Prosonic T Identifies a Warning
• the instrument continues to measure
• an error code is output in V9H0
If the Prosonic T Identifies a Warning
• the red LED flashes
• the instrument continues to measure
• an error code is output in V9H0
Code
Type
Cause and Removal
E 101
Alarm
Check sum error EEPROM/FRAM - Contact Hauser Service.
E 102
Warning
Check sum error EEPROM/FRAM - Contact Hauser Service.
E 103
Warning
Initialization starting. If error remains, initialization cannot be started.
E 106
Alarm
Download in progress – Wait until completed.
E 110- Alarm
Reset instrument, if error remains, electronic instrument error.
E 121
Contact Hauser Service.
E116
Alarm
Error with download – Carry out reset or restart download with corrected
data.
E125
Alarm
Defective sensor – Check sensor connection. Contact Hauser
Service if error remains.
E261
Alarm
Error in temperature sensor – Contact Hauser Service.
E 501
Alarm
Sensor electronics not recognized – Contact Hauser Service.
E 602
Warning
Linearization curve is rising continuously – Check manual linearization
curve. Does the volume increase with height?
E 604
Warning
Linearization curve has less than 2 points – Check manual linearization
curve and enter more points.
E 605
Alarm
Linearization table not available – Appears while entering the
linearization curve. Activate the linearization curve after entering all
points.
E 613
Warning
Simulation activated – Switch to normal operation after simulation is
completed. Simulation off: V9H6: 0
E 620
Warning
Current outside range – Check calibration and settings of the current
output.
E 641
Alarm
No usable echo
– Due to loss of echo (e.g. foam) or when measuring starts
– Check calibration and operating range
Contact Hauser Service if error remains.
E 661
Warning
High Temperature (greater than 176°F/80°C) – Check measuring
conditions.