Prosonic M FMU44 HART
Diagnostics and troubleshooting
Hauser
37
100%
0%
A
B
t →
A0038462
A
Expected result
B
Error occurred
1. Perform interference echo suppression (mapping).
2. In the
Process cond. (004)
function, select "Turb. surface" or "Add. agitator".
3. Increase the
output damping (058)
.
4. Select another installation position and/or a larger sensor.
Error: During filling or emptying, the measured value drops.
Example:
100%
0%
A
B
t →
A0038463
A
Expected result
B
Error occurred
1. Check the tank shape and correct it → "Dome ceiling" or "Horizontal cyl.".
2. If possible, do not select an installation position in the middle
3. If necessary, use a stilling well/ultrasound guide pipe
Error:
Echo loss (E641)
Example: