Prosonic M FMU44 HART
Mounting
Hauser
11
5.1.4
Installation conditions for the sensor for flow measurements
• Mount the measuring device on the upstream side immediately above the maximum
upper water level H
max
• Take the blocking distance into account
• Position the measuring device in the center of the flume or weir
• Align the sensor membrane so that it is parallel to the surface of the water
• Observe the installation clearance of the flume or weir
• Enter the "flow - level" ("Q/h curve") linearization curve via the FieldCare operating
program or manually via the local display
1 x b
b
BD
A
E
B
C
V
H
max
= F
0
0
A0038222
7
Khafagi-Venturi flume (example)
A
Khafagi-Venturi flume
B
Upstream side
C
Downstream side
BD Blocking distance of the sensor
E
Empty calibration (enter during commissioning)
H
max
Maximum upstream level
V
Flow
b
0
Width of Khafagi-Venturi flume
Содержание Prosonic M FMU44
Страница 52: ...www addresses endress com 71574097 71574097 ...