Setting the full-scale value
Works setting: at v ~ 2.5 m/s
Switches No. 8, 9, 10: OFF-OFF-ON
The current output supplies signals between 0/4 and 20 mA, corresponding to the
momentary value of the flow. By setting the full-scale, a flow is assigned to the current
of 20 mA. This setting always applies to both directions of flow (bidirectional). The
direction of flow is emitted at the status output with appropriate configuration.
In practice the maximum rate of flow that occurs is not always reliably known. There-
fore it is possible to extend up to 125% (500 Hz).
For the Promag 31 measuring system eight preset pulse-value steps can be selected
in terms of the nominal diameter. Setting is made by means of three miniature swit-
ches (see Chapter 4.2).
➤
Auxiliary input
The auxiliary input cannot be affected
by the miniature switches
Error reset and self test function of the display
In fiscal operation a pulse (3...30 V DC, min. 100 ms) resets a possible error.
Further more a display-self test runs for about 10 s.
Electrode Cleaning Circuit ECC (Option)
Conductive material build-up on the electrodes (e.g. magnetite) can lead to errors in
measurement. The electrode cleaning circuit (ECC) has, therefore, been developed to
prevent such a build-up. The cleaning cycles are carried out every 30 minutes for
2...5 secs each depending on the scanning frequency. If the Promag 31 measuring
system is equipped with the electrode cleaning circuit option (ECC), then this can be
switched on and off using the miniature switches on the amplifier board (see Fig. 44,
on page 42). When delivered from the factory, the electrode cleaning circuit is always
switched on. The ECC is not available with the FL version.
Caution!
If the ECC is switched off for a long period of time in an application with conductive
build-up, then material build-up in the measuring pipe can lead to measuring errors.
If there is a large concentration of build-up at one point, then, under certain
circumstances, switching on the ECC may not remove it. In such cases the measuring
pipe is to be cleaned and the build-up removed.
b
a02
8y
3
5
Measuring range for Promag 31 electronics
Flow rate Q ~ Medium velocity v
Maximum
full-scale value
20 mA current
Minimum
full-scale value
0 0.5
10
12.5 [m/s]
500 Hz
Fig. 38
4. Operation and Commissioning
Promag 31
32
Hauser
Содержание promag 31
Страница 4: ...Promag 31 4 Endress Hauser ...
Страница 22: ...2 Mounting and Installation Promag 31 22 Endress Hauser ...
Страница 28: ...Promag 31 28 Endress Hauser ...
Страница 44: ...5 Fault Location and Remedies Promag 31 44 Endress Hauser ...
Страница 56: ...6 Technical Data Promag 31 56 Endress Hauser ...
Страница 59: ......