Inlet and outlet runs
The sensor should be mounted away
from fittings liable to generate
turbulence (e.g. valves, elbows,
T-junctions).
Inlet run:
> 3...5 x DN
Outlet run: > 2 x DN
For fiscal use, the straight pipe
requirements are 5 x DN upstream and
2 x DN downstream, measured from the
meter flanges.
Mounting location
Correct measurement is only possible
when the pipe is full. Consequently the
following locations should be avoided:
No installation at the highest point
(air accumulation).
No installation immediately before an
open pipe outlet in a downward line. The
installation shown in Fig. 13, however,
permits such a location.
Partly filled pipes
For inclines a mounting similar to a drain
should be adopted. Do not mount at the
lowest point (risk of solids collecting).
Added security is offered by Empty Pipe
Detection (EPD). This option has an
extra electrode in the measuring pipe
(standard with Promag F sensor).
Note!
Here, too, the inlet and outlet lengths
should be maintained.
DN = pipe diameter
> 3...5 x DN
> 2 x DN
b
a028
y
0
9
Fig. 12
b
a02
8y
1
0
h > 2 x DN
Fig. 13
> 3...5 x DN
> 2 x DN
b
a028
y
1
1
Fig. 14
2. Mounting and Installation
Promag 31
14
Hauser
Содержание promag 31
Страница 4: ...Promag 31 4 Endress Hauser ...
Страница 22: ...2 Mounting and Installation Promag 31 22 Endress Hauser ...
Страница 28: ...Promag 31 28 Endress Hauser ...
Страница 44: ...5 Fault Location and Remedies Promag 31 44 Endress Hauser ...
Страница 56: ...6 Technical Data Promag 31 56 Endress Hauser ...
Страница 59: ......