Commissioning
Proline Prowirl F 200 PROFIBUS PA
78
Hauser
10.4.4 Configuring the analog inputs
The
Analog inputs
submenu guides the user systematically to the individual
Analog input
1 to n
submenu. From here you get to the parameters of the individual analog input.
Navigation
"Setup" menu → Analog inputs
‣
Analog inputs
‣
Analog input 1 to n
Channel
PV filter time
Fail safe type
Fail safe value
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Channel
–
Select the process variable.
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Temperature
• Calculated
saturated steam
pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow
difference
• Reynolds number
• Density
• Pressure
• Specific volume
• Degrees of
superheat
Volume flow
PV filter time
–
Specify the time to suppress
signal peaks. During the
specified time the analog input
does not respond to an erratic
increase in the process
variable.
Positive floating-
point number
0
Fail safe type
–
Select the failure mode.
• Fail safe value
• Fallback value
• Off
Off
Fail safe value
In
Fail safe type
parameter,
the
Fail safe value
option is
selected.
Specify the values to be output
when an error occurs.
Signed floating-point
number
0
*
Visibility depends on order options or device settings