Proline Prowirl F 200 PROFIBUS PA
Diagnostics and troubleshooting
Hauser
151
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
082 Data storage
1. Change main electronic module
2. Change sensor
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Temperature
• Volume flow
Measured variable status
Quality
Bad
Quality substatus
Maintenance alarm
Coding (hex)
0x24 to 0x27
Status signal
F
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
083 Memory content
1. Restart device
2. Restore S-Dat data
3. Change sensor
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Temperature
• Volume flow
Measured variable status
Quality
Bad
Quality substatus
Maintenance alarm
Coding (hex)
0x24 to 0x27
Status signal
F
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
114 Sensor leaky
Change DSC sensor
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Volume flow
Measured variable status
Quality
Bad
Quality substatus
Maintenance alarm
Coding (hex)
0x24 to 0x27
Status signal
F
Diagnostic behavior
Alarm