Proline Prowirl F 200 PROFIBUS PA
Commissioning
Hauser
109
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Assign status
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Status
option is
selected in the
Switch
output function
parameter.
Select device status for switch
output.
• Low flow cut off
• Digital output 2
Low flow cut off
Switch-on value
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Limit
option is selected.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
• 0 m³/h
• 0 ft³/h
Switch-off value
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Limit
option is selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
• 0 m³/h
• 0 ft³/h
Switch-on delay
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
0.0 s
Switch-off delay
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Define delay for the switch-off
of status output.
0.0 to 100.0 s
0.0 s
Failure mode
–
Define output behavior in
alarm condition.
• Actual status
• Open
• Closed
Open
Invert output signal
–
Invert the output signal.
• No
• Yes
No
*
Visibility depends on order options or device settings
10.5.5 Configuring the totalizer
In the
"Totalizer 1 to n" submenu
the individual totalizer can be configured.
Navigation
"Setup" menu → Advanced setup → Totalizer 1 to n
‣
Totalizer 1 to n
Assign process variable
Unit totalizer
Control Totalizer 1 to n
Totalizer operation mode
Failure mode