Connecting the supply
voltage or signal cable
The terminal assignment and the connection data for the supply voltage are identical for all devices, regardless
of the device version (type code).
!
Note!
A graphic illustration of the electrical connections is provided on Page 7.
Terminal assignment /connection data
Service connector
The service connector (for connection, see Fig. 3 to Fig. 7, e) is only used to connect service interfaces
approved by Hauser.
#
Warning!
The service connector may not be connected in a potentially explosive atmosphere.
Technical data
Dimensions
The dimensions of the Ex transmitter housing and the sensor correspond to the standard versions.
Please refer to the Technical Information for these dimensions.
!
Note!
Associated "Technical Information":
Proline Prosonic Flow 92F
TI073D/06/…
Control drawings
Hauser Reinach hereby declares that the product is in conformitywith the requirements of the
FACTORY MUTUAL standards.
!
Note!
The "Documentation/Important Information" folder provided with the measuring device contains a CD-ROM
with all the Control Drawings.
Terminals
1 (+)
2 (–)
3 (+)
4 (–)
Prosonic 92F**-***********A
Prosonic 92F**-***********W
Terminal
designation
Transmitter power supply /
4 to 20 mA HART
Optional
pulse/status output
Safety-related
values
35 V (U
max
= 250 V)
35 V (U
max
= 250 V)
Terminals
1 (+)
2 (–)
Prosonic 92F**-***********H
Terminal
designation
PROFIBUS PA
Safety-related
values
U = 35 V
(U
max
= 250 V)
Terminals
1 (+)
2 (–)
Prosonic 92F**-***********K
Terminal
designation
FOUNDATION Fieldbus
Safety-related
values
U = 35 V
(U
max
= 250 V)