Post-connection check
Perform the following checks after completing electrical installation of the measuring device:
Device condition and specifications
Notes
Are cables or the device damaged (visual inspection)?
-
Electrical connection
Notes
Do the cables comply with the specification?
FOUNDATION Fieldbus
Do the cables have adequate strain relief?
-
Is the cable type route completely isolated?
Without loops and crossovers?
-
Are the power-supply and signal cables correctly connected?
See the wiring diagram inside the
cover of the connection
compartment
Are all screw terminals firmly tightened?
-
Have the measures for grounding/potential equalization been correctly
implemented?
Are all cable entries installed, firmly tightened and correctly sealed?
Cables looped as "water traps"?
Are all housing covers installed and firmly tightened?
-
Electrical connection of FOUNDATION Fieldbus H1
Notes
Are all the connecting components (T-boxes, junction boxes, connectors, etc.)
correctly connected with each other?
-
Has each fieldbus segment been terminated at both ends with a bus
terminator?
-
Has the max. length of the fieldbus cable been observed in accordance with
the FOUNDATION Fieldbus specifications?
Has the max. length of the spurs been observed in accordance with the
FOUNDATION Fieldbus specifications?
Is the fieldbus cable fully shielded (90%) and correctly grounded?