Wiring
Proline Promag 55 FOUNDATION Fieldbus
50
Hauser
4.6
Degree of protection
The devices fulfill all the requirements for IP 67 (NEMA 4X).
Compliance with the following points is mandatory following installation in the field or servicing,
in order to ensure that IP 67 protection (NEMA 4X) is maintained:
• The housing seals must be clean and undamaged when inserted into their grooves. The seals must
be dried, cleaned or replaced if necessary.
• All housing screws and screw covers must be firmly tightened.
• The cables used for connection must be of the specified external diameter
• Tighten cable glands to prevent leakages.
• The cables must loop down before they enter the cable entries ("water trap"). This arrangement
prevents moisture penetrating the entry. Always install the measuring device in such a way that
the cable entries do not point up.
• Close off unused cable entries using suitable insert plugs.
• Do not remove the grommet from the cable entry.
a0001914
Fig. 38:
Installation instructions, cable entries
"
Caution!
Do not loosen the screws of the sensor housing as otherwise the degree of protection guaranteed by
Hauser no longer applies.
!
Note!
The sensor Promag S can also be supplied with IP 68 rating (permanent immersion in water to a
depth of 3 meters). In this case the transmitter must be installed remote from the sensor.
When using the measuring device in:
• pipes with cathodic protection
The device is installed in the pipeline in such a way that it is
potential-free.
Using a ground cable (copper wire, min. 6 mm² (0.0093 in
2
)),
only the two pipe flanges are connected. When doing so, the
ground cable is mounted directly on the conductive flange
coating using flange screws.
Please note the following during installation:
• The relevant regulations for potential-free installations must
be observed.
• There must not be an electrically conductive connection
between the piping and the device.
• The mounting material must be able to withstand the relevant
torques.
A0011896
Fig. 37:
Potential equalization and cathodic
protection
1
Isolation transformer power supply
2
Electrically isolated
Operating conditions
Potential equalization
1
2
2
a
b