Technical data
Proline Promag 55 FOUNDATION Fieldbus
102
Hauser
VCRs
10.1.5
Power supply
Electrical connections
Supply voltage
20 to 260 V AC, 45 to 65 Hz
20 to 64 V DC
Cable entries
Power supply and signal cable (inputs/outputs):
• Cable gland M20 × 1.5 (8 to 12 mm / 0.31 to 0.47 inch)
• Cable gland sensor for armored cables M20 × 1.5 (9.5 to 16 mm / 0.37 to 0.63 inch)
• Cable entries for thread ½" NPT, G ½"
Connecting cable for remote version:
• Cable gland M20 × 1.5 (8 to 12 mm / 0.31 to 0.47 inch)
• Cable gland sensor for armored cables M20 × 1.5 (9.5 to 16 mm / 0.37 to 0.63 inch)
• Cable entries for thread ½" NPT, G ½"
Cable specifications
(remote version)
Power consumption
AC: <45 VA at 260 V AC; <32 VA at 110 V AC (incl. sensor)
DC: <19 W (including sensor)
Switch-on current:
• Max. 2.00 A (<700 ms) at 20 V AC
• Max. 2.28 A (<5 ms) at 110 V AC
• Max. 5.5 A (<5 ms) at 260 V AC
Power supply failure
Lasting min. 1 power cycle:
• EEPROM or HistoROM/T-DAT saves measuring system data if power supply fails
• HistoROM/S-DAT: exchangeable data storage device which stores sensor characteristic data
(nominal diameter, serial number, calibration factor, zero point etc.)
Potential equalization
Discrete state 0
→
Discrete state 27
Permanent Storage "OFF"
Discrete state 0
→
Discrete state 28
Permanent Storage "ON"
Status change
Action
VCRs (total 48)
48
Permanent Entries
1
Client VCRs
0
Server VCRs
24
Source VCRs
23
Sink VCRs
0
Subscriber VCRs
23
Publisher VCRs
23