Connecting the remote version
#
Warning!
• Risk of electric shock. Switch off the power supply before opening the device. Do
not
install or
wire the device while it is connected to the power supply. Failure to comply with this precaution
can result in irreparable damage to the electronics.
• Risk of electric shock. Connect the protective conductor to the ground terminal on the housing
before the power supply is applied.
"
Caution!
• Only sensors and transmitters with the same serial number may be connected with each other.
Communication problems may occur if this is not adhered to.
• Risk of damaging the coil driver. Do not connect or remove the coil cable until the power supply
has been switched off.
4.3.1
Connecting the sensor
Procedure
1.
Transmitter: Remove the cover from the connection compartment (a).
2.
Sensor: Remove the cover from the connection housing (b).
3.
Feed the signal cable (c) and coil current cable (d) through the appropriate cable entries.
"
Caution!
Secure the connecting cable (see "Length of connecting cable"
4.
Terminate the signal and coil current cable in accordance with the table:
Promag S
→
Please see the "Cable termination" table
Promag S
→
Please see the "Cable termination" table
5.
Set up the wiring between the sensor and the transmitter.
The wiring diagram applicable to your device can be found:
• in the relevant diagram:
28 (Promag S);
29 (Promag H)
• in the cover of the sensor and transmitter.
!
Note!
The cable shields of the Promag H sensor are grounded using strain relief clamps
"
Caution!
Insulate the cable shields that are not connected. This eliminates the risk of short-circuits with
neighboring cable shields inside the connection housing.
6.
Transmitter: Secure the cover on the connection compartment (a).
7.
Sensor: Mount the cover on the connection housing (b).