Proline Promag 55 FOUNDATION Fieldbus
Wiring
Hauser
41
Cable termination in remote version
Promag S
Terminate the signal and coil current cables as shown in the figure below (Detail A).
Fit the fine-wire cores with wire end ferrules (Detail B).
"
Caution!
When fitting the connectors, pay attention to the following points:
•
Signal cable
→
Make sure that the wire end ferrules do not touch the wire shields on the sensor side!
Minimum distance = 1 mm / 0.04" (exception "GND" = green cable)
•
Coil current cable
→
Insulate one core of the three-core wire at the level of the core reinforcement; you only require two cores for the connection.
TRANSMITTER
Signal cable
Coil current cable
A0002687-ae
A0002688-ae
SENSOR
Signal cable
Coil current cable
A0002646-ae
A0002650-ae
m
= Cable end sleeve red, Ø 1.0 mm (0.04 in)
n
= Cable end sleeve white, Ø 0.5 mm (0.02 in)
* = Stripping for armored cables only
A
B
GND
m
m
m
m
n
n
n
n
80 (3.15)
50 (1.97)
17 (0.67)
8 (0.31)
100 (3.94)*
mm (inch)
A
B
m
m
m
90 (3.54)*
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
mm (inch)
A
m
n
n
n
GND
mm (inch)
80 (3.15)
50 (1.97)
8 (0.31)
³
1 (0.04)
170 (6.69)*
20 (0.79)*
17 (0.67)
B
A
m
m
m
mm (inch)
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
160 (6.30)*
20 (0.79)*