BA124D/06/en/12.07
71065432

Valid as of version:
V 3.05.XX (Device software)

Operating Instructions

Proline Promag 55
PROFIBUS PA

Electromagnetic Flow Measuring System

8

Содержание Proline Promag 55 PROFIBUS PA

Страница 1: ...BA124D 06 en 12 07 71065432 Valid as of version V 3 05 XX Device software Operating Instructions Proline Promag 55 PROFIBUS PA Electromagnetic Flow Measuring System 8...

Страница 2: ...cable and the fieldbus cable The terminal assignment The potential matching and degree of protection Display and operating elements Page 58 The available display and operating elements of the local di...

Страница 3: ...ou can configure as necessary with the aid of the function matrix and customize to suit your process parameters Note All functions are described in detail including the function matrix itself in the D...

Страница 4: ...forward commissioning n 3001 3001 E Esc E XXX XXX XX E m o p Deliver Settings y Selection pre settings Actual Settings 0402 Unit Volume Flow Volume Flow Mass Flow Quit Configure another unit NO YES Un...

Страница 5: ...ting the transmitter 47 4 4 2 Fieldbus connector 49 4 4 3 Terminal assignment 50 4 5 Potential equalization 51 4 5 1 Standard case 51 4 5 2 Special cases 52 4 6 Degree of protection 55 4 7 Post connec...

Страница 6: ...3 Process error messages 109 9 3 1 Displaying the device status on PROFIBUS 109 9 3 2 List of process error messages 109 9 4 Process errors without messages 110 9 5 Spare parts 111 9 5 1 Removing and...

Страница 7: ...ult in changes of the chemical resistance properties Therefore Endress Hauser can not guarantee or accept liability for the chemical resitance properties of the fluid wetted materials in a specific ap...

Страница 8: ...ion form at the back of these Operating Instructions Warning Do not return a measuring device if you are not absolutely certain that all traces of hazardous substances have been removed e g substances...

Страница 9: ...the specifications on the order confirmation for the meanings of the individual letters and digits 2 Power supply frequency Power consumption 3 Additional functions and software 4 Available inputs an...

Страница 10: ...on special products 7 Permitted ambient temperature range 8 Please refer to operating instructions documentation 9 Reserved for additional information on device version approvals certificates 10 Calib...

Страница 11: ...l assignment 6 Version of device software currently installed incl language group 7 Type of communication installed 8 PROFIBUS ID No 9 Date of installation 10 Current updates to data specified in poin...

Страница 12: ...measuring system is in conformity with the EMC requirements of the Australian Communications and Media Authority ACMA The flowmeter has successfully passed all the test procedures carried out and is...

Страница 13: ...ith PTFE linings Special notes on flanged devices Caution The wooden covers mounted on the flanges before the device leaves the factory protect the linings on the flanges during storage and transporta...

Страница 14: ...reliably against impact for storage and transportation The original packaging provides optimum protection The storage temperature corresponds to the operating temperature range of the measuring trans...

Страница 15: ...pipeline Risk of air accumulating Directly upstream from a free pipe outlet in a vertical pipeline a0003202 Fig 7 Mounting location Installing pumps Do not install the sensor on the intake side of a...

Страница 16: ...s advisable to install a cleaning valve a0003204 Fig 9 Installation in partially filled pipe Down pipes Install a siphon or a vent valve downstream of the sensor in down pipes longer than 5 meters 16...

Страница 17: ...stems and when using empty pipe detection For sludge containing sand or stones and where the solids cause sedimentation a0003206 Fig 11 Vertical orientation Horizontal orientation The measuring electr...

Страница 18: ...r to ensure measuring accuracy Inlet run 5 x DN Outlet run 2 x DN a0003210 Fig 13 Inlet and outlet runs 3 2 5 Vibrations Secure and fix both the piping and the sensor if the vibrations are severe Caut...

Страница 19: ...install the sensor in larger diameter pipes The resultant increase in the rate of flow improves measuring accuracy with very slow moving fluids The nomogram shown here can be used to calculate the pr...

Страница 20: ...be increased if necessary by reducing the nominal diameter of the sensor through the use of adapters Page 19 Promag S Flow rate characteristic values Promag S SI units Nominal diameter Recommended flo...

Страница 21: ...n 0 50 gal min 1 7 to 190 gal min 0 75 gal min 2 10 to 300 gal min 1 25 gal min 2 16 to 500 gal min 2 0 gal min 3 24 to 800 gal min 2 5 gal min 4 40 to 1250 gal min 4 0 gal min 5 60 to 1950 gal min 7...

Страница 22: ...o 1100 dm3 min 5 dm3 min 65 60 to 2000 dm3 min 8 dm3 min 80 90 to 3000 dm3 min 12 dm3 min 100 145 to 4700 dm3 min 20 dm3 min Flow rate characteristic values Promag H US units Nominal diameter Recommen...

Страница 23: ...ation between sensor and transmitter if necessary The permissible cable length Lmax depends on the fluid conductivity Fig 17 Fig 18 Promag S a0006116 ae Fig 17 Permitted lengths for connecting cable i...

Страница 24: ...Page 26 ff Information on the installation of additional ground disks Page 25 a0004296 Fig 19 Installing the Promag S sensor Seals Comply with the following instructions when installing seals Hard rub...

Страница 25: ...installed if necessary to protect the measuring tube lining from excessive abrasion Caution When using these disks incl seals the total fitting length is increased The dimensions are provided in the...

Страница 26: ...0 8 x M 16 27 43 40 32 80 PN 16 8 x M 16 13 34 53 48 40 80 PN 40 8 x M 16 34 53 48 40 100 PN 16 8 x M 16 14 36 57 51 43 100 PN 40 8 x M 20 50 78 70 59 125 PN 16 8 x M 16 19 48 75 67 56 125 PN 40 8 x M...

Страница 27: ...ass 300 4 x 11 25 23 2 Class 150 4 x 5 8 16 35 32 2 Class 300 8 x 5 8 8 1 17 16 3 Class 150 4 x 5 8 15 32 58 49 44 3 Class 300 8 x 19 35 31 28 4 Class 150 8 x 5 8 11 23 41 37 31 4 Class 300 8 x 30 49...

Страница 28: ...1 28 80 10K 8 x M 16 23 38 32 29 80 20K 8 x M 20 35 57 46 42 100 10K 8 x M 16 29 47 38 35 100 20K 8 x M 20 48 75 58 56 125 10K 8 x M 20 51 80 66 60 125 20K 8 x M 22 79 121 103 91 150 10K 8 x M 20 63 9...

Страница 29: ...0 C 300 F Note You will find information on permissible temperature ranges on Page 122 Insulation Pipes generally have to be insulated if they carry very hot fluids in order to avoid energy losses and...

Страница 30: ...s connections with aseptic gasket seals Weld nipples DIN 11850 ODT SMS Clamp ISO 2852 DIN 32676 L14 AM7 coupling DIN 11851 DIN 11864 1 SMS 1145 flange DIN 11864 2 C DN 40 to 100 1 to 4 process connect...

Страница 31: ...rings can be ordered separately from Endress Hauser as accessories Page 99 When placing the order make certain that the ground ring is compatible with the material used for the electrodes Otherwise th...

Страница 32: ...al from the pipe 2 Weld the process connection to the pipe 3 Reinstall the sensor in the pipe Make sure that everything is clean and that the seal is correctly seated Note If thin walled foodstuffs pi...

Страница 33: ...Lower the housing into position and reengage the bayonet catch 6 Retighten the two securing screws a0004302 Fig 24 Turning the transmitter housing aluminum field housing Turning the stainless steel fi...

Страница 34: ...ousing 2 Press the latches on the side of the display module and pull the module out of the electronics compartment cover 3 Turn the display to the desired position max 4 x 45 in both directions and p...

Страница 35: ...Install the device at a shady location Avoid direct sunlight Always install the wall mount housing in such a way that the cable entries are pointing down Mounted directly on the wall 1 Drill the hole...

Страница 36: ...the panel Afterwards tighten the locking nuts Additional support is not necessary a0001131 ae Fig 28 Panel Installation wall mount housing Pipe mounting The assembly should be performed by following t...

Страница 37: ...ough the pipe Is the position of the measuring electrode plane correct Horizontal Is the position of the empty pipe detection electrode correct Page 17 Were all threaded fasteners tightened to the spe...

Страница 38: ...air cables it is permissible to operate multiple fieldbuses with the same degree of protection on one cable No other circuits are permissible in the same cable Practical experience has shown that cabl...

Страница 39: ...per segment in non Ex areas or a maximum of 10 users in an Ex area EEx ia IIC is possible The actual number of users must be determined during configuration 4 1 5 Bus termination The start and end of...

Страница 40: ...ed many times Keep the stripped and twisted lengths of cable shield to the terminals as short as possible This approach which provides the best electromagnetic compatibility and personal safety can be...

Страница 41: ...Transmitter Loosen the screws and remove the cover a from the connection compartment 2 Sensor Remove the cover b from the connection housing 3 Feed the signal cable c and coil current cable d through...

Страница 42: ...ection compartment wall mount housing b Cover of connection housing sensor c Signal cable d Coil current cable n c unconnected insulated cable shields Terminal no and cable colors 6 5 brown 7 8 white...

Страница 43: ...ll mount housing b Cover of connection housing sensor c Signal cable d Coil current cable n c unconnected insulated cable shields Terminal no and cable colors 6 5 brown 7 8 white 4 green 36 37 yellow...

Страница 44: ...Coil current cable Insulate one core of the three core wire at the level of the core reinforcement you only require two cores for the connection TRANSMITTER Signal cable Coil current cable a0002687 a...

Страница 45: ...re wire at the level of the core reinforcement you only require two cores for the connection On the sensor side reverse both cable shields approx 15 mm over the outer jacket The strain relief ensures...

Страница 46: ...176 F Cable permanently routed 40 to 80 C 40 to 176 F Cable cross section max 2 5 mm2 14 AWG a0003194 Fig 32 Cable cross section a Signal cable b Coil current cable 1 Core 2 Core insulation 3 Core shi...

Страница 47: ...ocal voltage supply and frequency Also observe the national regulations governing the installation of electrical equipment Procedure Fig 33 1 Unscrew the connection compartment cover a from the transm...

Страница 48: ...otective ground d Fieldbus cable Terminal No 26 PA with reverse polarity protection Terminal No 27 PA with reverse polarity protection e Fieldbus cable shield ground terminal Observe the following the...

Страница 49: ...ntly e g when constructing new star distributors using 4 channel or 8 channel distribution modules The device can therefore be supplied with the option of a ready mounted fieldbus connector Fieldbus c...

Страница 50: ...rly true for offset boxes when these are connected to a PROFIBUS PA measuring device using a plug in cable In such a case use a metallic plug in which the cable shielding is attached to the plug housi...

Страница 51: ...d If the process connections are made of a synthetic material ground rings have to be used to ensure that potential is equalised see Page 31 Ground rings can be ordered with the main product structure...

Страница 52: ...se see diagram The ground cable for flange to flange connections can be ordered separately as an accessory from Endress Hauser Page 99 DN 300 12 The ground cable is in direct connection with the condu...

Страница 53: ...s it is possible that due to the grounding plan of a system matching currents flow over the reference electrodes This can lead to destruction of the sensor e g through electrochemical decomposition of...

Страница 54: ...ting material used does not establish a conductive connection between the pipe and the measuring device and that the mounting material withstands the torques applied when the threaded fasteners are ti...

Страница 55: ...ge 119 Tighten cable glands to prevent leakages The cables must loop down before they enter the cable entries water trap This arrangement prevents moisture penetrating the entry Always install the mea...

Страница 56: ...iagram inside the cover of the terminal compartment Are all screw terminals firmly tightened Have the measures for grounding potential equalization been correctly implemented Page 51 Are all cable ent...

Страница 57: ...cturers for these purposes 3 Jumpers miniature switches for hardware settings Page 66 You can make the following hardware settings using a jumper or miniature switches on the I O board Address mode co...

Страница 58: ...e liquid crystal display shows measured values dialog texts fault messages and notice messages The display as it appears when normal measuring is in progress is known as the HOME position operating mo...

Страница 59: ...ages Display and presentation of system process errors Page 63 a0004755 Fig 43 Typical display for normal operating mode HOME position 1 Main line shows main measured values e g flow 2 Supplementary l...

Страница 60: ...le via PLC Class 1 master a0002322 Display value DISPLAY_VALUE module with status GOOD a0002321 Display value DISPLAY_VALUE module with status UNC uncertain a0002320 Display value DISPLAY_VALUE module...

Страница 61: ...E F 3 O S Select a group e g CONTROL F 4 O S Select a function group e g BASIC CONFIGURATION F 5 Select a function e g LANGUAGE and change parameter enter numerical values O S Select or enter release...

Страница 62: ...in progress i e the current measured values are output via the signal outputs in the normal way If the power supply fails all preset and parameterized values remain safely stored in the EEPROM 5 3 2...

Страница 63: ...notice message 3 Error designation 4 Error number 5 Duration of most recent error occurrence hours minutes seconds 5 4 2 Error message type Error message type The measuring device always assigns syste...

Страница 64: ...agnosis of intelligent field devices By using status information you also have a simple but effective tool for monitoring devices The Proline flowmeters are accessed via a service interface or via the...

Страница 65: ...ILE VERSION function 6160 DEVICE ID function 6162 GSD file information Promag 53 55 GSD file Extended Format recommended Standard Format eh3x1527 gsd eh3_1527 gsd Note Before configuring the PROFIBUS...

Страница 66: ...Page 112 3 Configure the hardware write protection accordingly with the aid of the jumpers see Figure 4 Installation of the I O board is the reverse of the removal procedure a0001359 Fig 46 Switching...

Страница 67: ...ed off before you remove the cover of the electronics compartment 1 Loosen the the securing clamp with an Allen key 3 mm 2 Unscrew the cover of the electronics compartment from the transmitter housing...

Страница 68: ...rational The measuring device performs a number of post switch on self tests As this procedure progresses the following sequence of messages appears on the local display Normal measuring mode commence...

Страница 69: ...up menu guides you systematically through the setup procedure for all the major device functions that have to be configured for standard measuring operation a0005958 en Fig 48 Quick Setup for straight...

Страница 70: ...transmitted via PROFIBUS m The DELIVERY SETTINGS option sets every selected unit to the factory setting The ACTUAL SETTINGS accepts the units you configured beforehand n Only units not yet configured...

Страница 71: ...B QUICK SETUP N QUICK SETUP COMMUNICATION 1006 Function No Function name Setting to be selected P to next function with F 1006 QUICK SETUP COMMUNICATION YES After F is pressed by way of confirmation t...

Страница 72: ...ce Options OFF SET UNITS transmission is started by pressing F key Caution Activating this function can cause a sudden change of the measured variables transmitted to the PROFIBUS master Class 1 this...

Страница 73: ...points Note For information on installing and removing the T DAT Seite 111 ff a0001221 en Fig 50 Data backup transmission with T DAT SAVE LOAD function Information on the LOAD and SAVE options availa...

Страница 74: ...low The following preconditions must be met Software option Solids content flow F CHIP DISPLAY_VALUE Option 2 Page 90 A density meter e g Gammapilot M from Endress Hauser for recording total fluid den...

Страница 75: ...able limit values to the solids flow see the following examples Case study 1 You wish to configure the totalizer for totalizing the complete solid mass flow e g in tons 1 Open the ASSIGN function of t...

Страница 76: ...ers without reference values Reference values should always be obtained immediately after commissioning This ensures that the reference values saved are values pertaining to the original condition of...

Страница 77: ...ropriate software for example using the Endress Hauser software packages FieldCare with the Flow Communication FXA193 291 DTM and Fieldsafe Module Function group diagnostic parameters Possible causes...

Страница 78: ...RATION 610 TAG NAME 6100 3 Configuring the fieldbus address Software addressing using the local display operating program BASIC FUNCTION G PROFIBUS PA GCA CONFIGURATION 610 FIELDBUS ADDRESS 6101 Hardw...

Страница 79: ...ECTIONAL the positive and negative flow components 7 Configuration of Totalizers 1 to 3 The measuring device has three totalizers The following example describes the configuration of the totalizer usi...

Страница 80: ...the operating mode Select the operating mode GSD file which should be used for cyclic communication with the PROFIBUS master Class 1 BASIC FUNCTION G PROFIBUS PA GCA OPERATION 614 SELECTION GSD 6140 S...

Страница 81: ...ce functionality Use this GSD file to access the complete functionality of the measuring device In this way device specific measured variables and functionalities are thus completely available in the...

Страница 82: ...acturers can be interchanged with the profile GSD file without the need to reconfigure interchangeability The following modules are supported with the Profile GSD file Name of the PROFIBUS Profile GSD...

Страница 83: ...se the GSD file with the extended format EH3x1527 gsd However if the installation or the configuration of the device fails with this format then use the standard GSD EH3_1527 gsd Example for the confi...

Страница 84: ...do not have to adjust the configuration of the PROFIBUS network in the automation system Procedure after replacing the measuring devices 1 Set the same old device address FIELDBUS ADDRESS 6101 functio...

Страница 85: ...properties The modules are permanently assigned to the slots i e the sequence or arrangement of the modules must be observed when configuring the modules see following table Gaps between configured mo...

Страница 86: ...es in the form of floating point numbers in accordance with the IEEE 754 standard The fifth byte contains standardized status information corresponding to the measured variable Further information on...

Страница 87: ...e measuring device If the measured variable is selected even if the additional software is not installed the value 0 is transmitted to the PROFIBUS master Class 1 for the measured variable Factory set...

Страница 88: ...BASIC FUNCTION G PROFIBUS PA GCA TOTALIZER 613 SELECT TOTALIZER 6130 Selection of a totalizer CHANNEL 6133 Selection of measured variable Possible settings Factory setting SETTOT_TOTAL module The mod...

Страница 89: ...escription of the SETTOT function refer to SETOT_TOTAL module Page 88 MODETOT function In the MODETOT function the totalizer can be configured via control variables The following settings are possible...

Страница 90: ...y itself or using an operating program e g FieldCare Output data Option 2 Density value for calculation of mass flow If the density value transmitted to the device is to be used for the continuous cal...

Страница 91: ...les CONTROL_BLOCK 0 2 Positive zero return ON 0 3 Positive zero return OFF 0 8 UNIDIRECTIONAL measuring mode 0 9 BIDIRECTIONAL measuring mode 0 24 Run UNIT TO BUS function Control variables that are e...

Страница 92: ...is variable it consists of several individual modules In the GSD file the individual modules are described with their individual properties The modules are permanently assigned to the slots i e the s...

Страница 93: ...me flow factory setting 2 SETTOT_MODETOT_TOTAL 5 2 Totalizer function block 1 TOTAL output variable volume flow factory setting SETTOT totalizer control MODETOT totalizer configuration 3 SETTOT_MODETO...

Страница 94: ...out cyclically by the measuring device by means of Analog Input function block 1 The totalizer is configured without configuration In other words in this example it only returns the totalizer value fo...

Страница 95: ...device via special SAPs Therefore the number of Class 2 masters that can communicate with a device simultaneously is limited to the number of SAPs available for this data transmission The use of a Cl...

Страница 96: ...tivated if required Performing empty pipe and full pipe adjustment EPD 1 Select the appropriate function in the function matrix HOME F R BASIC FUNCTION F R PROCESSPARAMETER F R ADJUSTMENT F EPD ADJUST...

Страница 97: ...le 6 10 1 HistoROM S DAT sensor DAT The S DAT is an exchangeable data storage device in which all sensor relevant parameters are stored i e diameter serial number calibration factor zero point 6 10 2...

Страница 98: ...BUS PA 98 Endress Hauser 7 Maintenance No special maintenance work is required 7 1 Exterior cleaning When cleaning the exterior of measuring devices always use cleaning agents that do not attack the s...

Страница 99: ...fications Approvals Degree of protection version Cable type for the remote version Cable entries Display power supply operation Software Outputs inputs 55XXX XXXXX Accessory Description Order code Mou...

Страница 100: ...ting flowmeters in the field When used in conjunction with the FieldCare software package test results can be imported into a database printed and used for official certification Contact your Endress...

Страница 101: ...defective Order spare parts Page 111 Error messages on display Errors which occur during commissioning or measuring operation are displayed immediately Error messages consist of a variety of icons Th...

Страница 102: ...ted with a bus terminator at both ends start and finish Otherwise there may be interference in communication Current consumption permitted feed current Check the current consumption of the bus segment...

Страница 103: ...ueried using an operating program e g FieldCare Function block SUPERVISION SYSTEM OPERATION ACTUAL SYSTEM CONDITION Display in the PROFIBUS master system cyclic data transmission If the AI or TOTAL mo...

Страница 104: ...e HEX Quality status Quality substatus Limits 0x4C 0x4D 0x4E UNCERTAIN Initial Value OK Low High No Device status message local display PROFIBUS measured value status Extended diagnostic message in th...

Страница 105: ...T is compatible with the existing electronics Check the Spare part set number Hardware revision code 3 Replace measuring electronics boards if necessary Spare parts Page 111 ff 4 Plug the S DAT into t...

Страница 106: ...must be replaced Page 111 ff No 2xx Error in DAT no communication 205 S LOAD T DAT 205 0x0F BAD Device Failure Constant Save to T DAT failed Cause Data backup downloading to T DAT failed or error when...

Страница 107: ...WNLO ACT 502 0x48 0x49 0x4A UNCERTAIN Substitute set substitute set of failsafe status O K Low High Upload download of device data active Cause Uploading or downloading the device data via configurati...

Страница 108: ...s SUPERVISION SYSTEM OPERATION SIM MEASURAND OFF 698 S DEV TEST ACT 698 0x60 0x61 0x62 UNCERTAIN Simulated Value manually specified value O K Low High Device test via Fieldcheck active Cause The measu...

Страница 109: ...ss conditions of the plant 2 Fill the measuring tube 461 P ADJ NOT OK 461 0x40 0x41 0x42 UNCERT AIN Non specific uncertain status O K Low High EPD adjustment not possible Cause EPD adjustment not poss...

Страница 110: ...grounding and potential equalization Page 51 ff 2 Check the fluid for presence of gas bubbles 3 Activate ON VALUE LOW FLOW function i e enter or increase on value BASIC FUNCTION PROCESSPARAMETER CONF...

Страница 111: ...directly from your Endress Hauser service organization by providing the serial number printed on the transmitter nameplate Page 9 Spare parts are shipped as sets comprising the following parts Spare...

Страница 112: ...fications Caution Use only original Endress Hauser parts Removing and installing the boards Fig 57 1 Unscrew cover of the electronics compartment from the transmitter housing 2 Remove the local displa...

Страница 113: ...Ribbon cable display module 2 Screws for electronics compartment cover 3 Aperture for installing removing boards 4 Power unit board 5 Amplifier board 5 1 Electrode signal cable sensor 5 2 Coil current...

Страница 114: ...r s specifications Caution Use only original Endress Hauser parts Removing and installing the boards Fig 58 1 Remove the screws and open the hinged cover 1 of the housing 2 Loosen the screws securing...

Страница 115: ...module 3 Ribbon cable display module 4 Screws for electronics compartment cover 5 Aperture for installing removing boards 6 Power unit board 7 Amplifier board 7 1 Electrode signal cable sensor 7 2 Coi...

Страница 116: ...g 59 The procedure for replacing the fuse is as follows 1 Switch off power supply 2 Remove power unit board Page 112 ff 3 Remove the protection cap 1 and replace the device fuse 2 Use only fuses of th...

Страница 117: ...ealth e g flammable toxic caustic carcinogenic etc Note You will find a preprinted Declaration of contamination form at the back of these Operating Instructions Warning Do not return a measuring devic...

Страница 118: ...Hard rubber lining for all applications with water especially for trinking water Natural rubber lining for all water applications for highly abrasive fluids e g for sludge with particles larger than...

Страница 119: ...260 V AC 45 to 65 Hz 20 to 64 V DC Cable entry Power supply and signal cables inputs outputs Cable gland M20 x 1 5 8 to 12 mm 0 31 to 0 47 inch Sensor cable gland for armored cables M20 x 1 5 9 5 to...

Страница 120: ...o r 2 mm s o r of reading With option brush electrodes 0 5 o r 2 mm s o r of reading Current output in addition typically 5 A Note Supply voltage fluctuations have no effect within the specified rang...

Страница 121: ...o 140 F Flange material stainless steel 40 to 60 C 40 to 140 F Caution Do not exceed the min and max temperatures for the lining of the measuring tube Medium temperature range Note the following point...

Страница 122: ...bber DN 65 to 600 2 to 24 0 to 60 C 32 to 140 F for natural rubber DN 65 to 600 2 to 24 20 to 50 C 4 to 122 F for polyurethane DN 25 to 600 1 to 24 20 to 180 C 4 to 356 F for PFA DN 25 to 200 1 to 8 r...

Страница 123: ...cm for all liquids incl demineralized water Note In the remote version the required minimum conductivity is also influenced by the length of the cable Page 23 Limiting medium pressure range nominal pr...

Страница 124: ...0 0 0 40 PTFE PFA 0 0 0 0 0 0 100 0 0 0 50 PTFE PFA 0 0 0 0 0 0 100 0 0 0 65 PTFE PFA 0 0 40 0 130 0 0 0 80 PTFE PFA 0 0 40 0 130 0 0 0 100 PTFE PFA 0 0 135 0 170 0 0 0 125 PTFE PFA 135 0 240 0 385 0...

Страница 125: ...6 F 302 F 356 F PTFE 0 0 0 1 5 1 PTFE PFA 0 0 0 0 0 0 1 5 0 0 0 PTFE PFA 0 0 0 0 0 0 1 5 0 0 0 1 PTFE PFA 0 0 0 0 0 0 1 5 0 0 0 2 PTFE PFA 0 0 0 0 0 0 1 5 0 0 0 PTFE PFA 0 0 0 6 0 1 9 0 0 0 3 PTFE PFA...

Страница 126: ...15 PN 40 6 5 10K 6 5 Class 150 6 5 PN 40 4 5 10K 4 5 Class 150 4 5 6 0 25 1 7 3 7 3 7 3 5 3 5 3 5 3 6 0 32 1 8 0 7 3 6 0 5 3 6 0 40 1 9 4 8 3 9 4 7 4 6 3 7 4 6 0 50 2 10 6 9 3 10 6 8 6 7 3 8 6 6 0 65...

Страница 127: ...Remote version without cable Sensor Transmitter mm inch EN DIN AS JIS ANSI EN DIN AS JIS ANSI Wall housing 15 PN 40 14 10K 14 Class 150 14 PN 40 10 10K 10 Class 150 10 13 25 1 16 16 16 12 12 12 13 32...

Страница 128: ...h Amerlock 400 paint finish JIS RSt37 2 S235JRG2 HII 1 0425 316L DN 350 with Al Zn protective coating DN 300 12 with Amerlock 400 paint finish AS 2129 DN 25 1 A105 or RSt37 2 S235JRG2 with Al Zn prote...

Страница 129: ...n the section Supplementary documentation Page 131 Fitted electrodes Promag S Reference and empty pipe detection electrodes Comes as standard with 1 4435 SS 316L Alloy C 22 tantalum Duplex tungsten ca...

Страница 130: ...ng the CE declaration of conformity C tick mark The measuring system meets the EMC requirements of the Australian Communications and Media Authority ACMA Ex approval Information on the currently avail...

Страница 131: ...alog output signal NAMUR NE 53 Software of field devices and signal processing devices with digital electronics 10 1 13 Ordering information The Endress Hauser service organization can provide detaile...

Страница 132: ...clic 95 Declaration of conformity CE mark 12 Degree of protection 55 121 Designated use 7 118 Device address configuring PROFIBUS PA 67 Device description files PROFIBUS PA 65 Device designation 9 118...

Страница 133: ...Inlet and outlet runs 18 Installing pumps 15 Mounting location 15 Nominal diameter and flow rate 20 Orientation vertical horizontal 17 Partially filled pipes 16 Supports foundations DN 300 19 Vibrati...

Страница 134: ...cation 15 Q Quick Setup Commissioning 4 69 Communication 71 Data back up of device data with T DAT 73 R Registered trademarks 12 Repair 8 117 Replacing Device fuse 116 Electronics boards installation...

Страница 135: ...e 121 Vibrations Measures to prevent vibrations 18 Shock and vibration resistance 121 W Wall mount housing installing 35 Weights 126 Welding work grounding welding equipment 32 Promag H with weld nipp...

Страница 136: ...Proline Promag 55 PROFIBUS PA Index 136 Endress Hauser...

Страница 137: ...__________________________________________ ______________________________________________________________________________________________________________ We hereby certify that this declaration is fil...

Страница 138: ...www endress com worldwide BA124D 06 en 12 07 71065432 FM SGML6 0 ProMoDo...