6.3.
Communication related errors
6.3.1.
Termination
Every Modbus segment has to be terminated at the ends with fieldbus resistors.
The integrated termination resistors of the CSF22 are switched off.
6.3.2.
Error counter
The device supervises the communication and has error counters. They are shown at the display or can be read via
Modbus.
Path: Menu/Expert/Diagnostics/System information/Modbus
The counter can be read via Modbus (Cap 7.3.4).