Liquistation CSF22 MODBUS
®
-Guideline
Hauser
© Copyright Dez. 2011
5
2.
Device identification
Manufacturer name:
Hauser
Model name:
Liquistation CSFxx
Device revision:
1
Physical layers supported:
RS485
Physical device category:
Transmitter, DC isolated bus device
The nameplate is located on the right side of the housing and indicates the model name, order codes, serial number
and software version. The device revision and Modbus address are shown in the setup menu.
Menu/Setup/General settings/Extended setup/Modbus
2.1.
Operation mode
At any time one of the following fieldbus protocols can be active:
•
Modbus RS485 (ASCII)
•
Modbus RS485 (RTU)
2.1.1.
ASCII
The data are transmitted as ASCII characters. They are readable for human.
Start
Address
Function
Data
LRC
End
1 character
2 characters
2 characters
N characters
2 characters
2 characters
= „:“
CRLF
Field
length
Info
Client
Server
Address
2 Byte
Identification of target device
Set by client
Copied from request
to response
LRC
2 Bytes
Modbus specification
Set by client
Set by server
2.1.2.
RTU
The data are transmitted as binary code. They are compact.
Address
Function
Data
CRC16
1 character
1 character
N characters
2 characters
0 = Broadcast
247 = Unicast
Hint:
Between two Modbus telegrams must be a delay of mind. 3.5 characters.
Field
length
Info
Client
Server
Address
1 Byte
Identification of target device
Set by client
Copied from request
to response
CRC16
2 Bytes
Modbus specification
Set by client
Set by server