Micropilot M FMR245 with PROFIBUS PA
Operation
Hauser
43
5.5.2
Device address
Selecting the device address
• Every PROFIBUS-PA device must be given an address. If the address is not set correctly, the
device will not be recognised by the process control system.
• A device address may appear only once within a particular PROFIBUS-PA network, see BA 198F.
• Valid device addresses are in the range 1 and 126. All devices are delivered from the factory with
the software address 126.
• The default address can be used to check the function of the device and connect it to an operating
PROFIBUS-PA system. Afterwards the address must be changed to allow other devices to be
connected to the network.
Software addressing
Software addressing comes into operation, when DIP-switch 8 is in the position "ON". BA 198F/
00/en, chap. 5.7 describes, how to set the address in this case.
In ToF Tool, the address can be set via the "
Set address
" function in the "
Device
" menu.
Hardware addressing
L00-FMU4xxxx-19-00-00-en-014
Hardware addressing comes into operation, when DIP switch 8 is in the position "HW (OFF)". In
this case the address is determinded by the position of DIP-switches 1 to 7 according to the
following table:
The new address becomes valid 10 seconds after switching.
It results a new device restart.
EN
DR
ESS
+HA
US
ER
MIC
RO
PIL
OT I
I
END
RES
S+HA
US
ER
MICR
OP
ILO
T II
IP 6
5
IP 65
Ord
er C
ode
:
Ser.-
No.:
Order Code:
Ser
.-No
.:
Mes
sbe
reich
Mea
surin
g ra
nge
Messbereich
Me
asur
ing r
ange
U 16
...36
V D
C
4...2
0 m
A
U 16...36
V DC
4...20 mA
max
. 20
m
max
. 20
m
Made in Ger
m
an
y Maulb
urg
Made in Ger
m
an
y Maulb
u
rg
T
>70
°C :
A
t >8
5°C
T
>70°
C :
A
t >8
5°C
on
off
SW
HW
4
1 2 3
5 6
8
7
1
2 3 4
5 6 7
8
2 + 8 = 10
ON
OFF
SW
HW
method of
addressing
address
Switch No.
1
2
3
4
5
6
7
Value in position "OFF"
0
0
0
0
0
0
0
Value in Position "ON"
1
2
4
8
16
32
64
Содержание Micropilot M FMR245
Страница 57: ...Micropilot M FMR245 with PROFIBUS PA Operation Endress Hauser 57 Tank linearisation MicropilotM en 307 ...
Страница 107: ...Micropilot M FMR245 with PROFIBUS PA Technical data Endress Hauser 107 ...
Страница 116: ...Micropilot M FMR245 with PROFIBUS PA Index 116 Endress Hauser ...
Страница 118: ...www endress com worldwide BA252F 00 en 05 08 71073076 CCS FM SGML 6 0 ProMoDo 71073076 ...