Micropilot M FMR245 with PROFIBUS PA
Trouble-shooting
Hauser
89
9.4
Application errors in solids
Error
Output
Possible cause
Remedy
A warning or alarm
has occurred.
Depending on the configuration
See table of error
messages (see Page 85)
1.
See table of error messages
(see Page 85)
Measured value
(00) is incorrect
L00-FMR250xx-19-00-00-en-019
Measured distance
(008) OK?
yes
→
1.
Check empty calibr. (005) and
full calibr. (006).
2.
Check linearisation:
→
level/ullage (040)
→
max. scale (046)
→
Check table
no
↓
An interference echo
may have been
evaluated.
yes
→
1.
Carry out tank mapping
→
basic setup
No change off
measured value on
filling/emptying
L00-FMR250xx-19-00-00-en-014
Interference echo from
installations, nozzle or
build up on the antenna
1.
Carry out tank mapping
→
basic setup
2.
If necessary, use top target
positioner to aim antenna better
to product surface (avoidance of
interference echo) (see Page 91)
3.
If necessary, clean antenna
4.
If necessary, select better
mounting position
100%
F m/ft
E m/ft
0%
t
→
D m/ft (008)
actual
expected
100%
0%
t
→
actual
expected
Содержание Micropilot M FMR245
Страница 57: ...Micropilot M FMR245 with PROFIBUS PA Operation Endress Hauser 57 Tank linearisation MicropilotM en 307 ...
Страница 107: ...Micropilot M FMR245 with PROFIBUS PA Technical data Endress Hauser 107 ...
Страница 116: ...Micropilot M FMR245 with PROFIBUS PA Index 116 Endress Hauser ...
Страница 118: ...www endress com worldwide BA252F 00 en 05 08 71073076 CCS FM SGML 6 0 ProMoDo 71073076 ...