Operation
Micropilot M FMR 240 with Foundation Fieldbus
46
E Hauser
5.5.5
Resource block
The resource block contains the parameters used to describe physical resources of the device. It has
no linkable inputs or outputs.
Operation
The resource block is opened by a click on the resource line.
If the NI-FBUS Configurator is being used, a series of file tabs appears on the screen. The files can
be opened to view and/or edit the parameters in the following table. A short description of the
parameter function appears on the side of the screen. A change in the parameter is stored by pressing
the WRITE CHANGES button when the block is out of service. Press the READ ALL button to check
the values stored in the device.
Parameters
The function of the resource block parameters not described here can can be taken from the
Foundation Fieldbus specification, see "
www.fieldbus.org
".
E+H_MICROPILOT_M_XXXXXXXX
RESOURCE_XXXXXX (RB2)
TRANSDUCER_XXXXXX (TBRL)
ANALOG_INPUT_1_XXXXXX (AI)
Parameter
Description
TAG_DESC
User description of the intended application of the block.
MODE_BLK
Lists the actual, target, permitted and normal operating modes of the block.
– Target: changes the operating mode of the block
– Actual: indicates the current operating mode of the block
– Permitted: states which operating modes are allowed
– Normal: indicates the normal operating mode of the block
The possible operating modes of the resources block are:
– AUTO: the block is operating as normal
– OOS: the block is out of service.
If the resource block is out of service, then all blocks within the device (resource) are
forced into the same status.
RS_STATE
Indicates the state of the resource block application state machine
– On-line: block in AUTO mode
– Standby: block in OOS mode
WRITE_LOCK
Indicates the status of DIP-switch WP
– LOCKED: device data can be modified
– NOT LOCKED: device data can be modified
RESTART
Allows a manual restart:
– UNINITIALISED: no status
– RUN: normal operational status
– RESOURCE: resets the resource block parameters
–
DEFAULTS: Resets all Foundation Fieldbus parameters within the device, but
not the manufacturer specific parameters.
– PROCESSOR: make a warm start of the processor
BLOCK_ERROR
Shows error status of software and hardware components
– Out-of-Service: the block is in OOS mode
– Simulation active: shows the setting of DIP-switch SIM
BLOCK_ALM
Shows any configuration, hardware, connection and system problems in the lock. The
cause of the alert is to be seen in the subcode field.