Operating menu
Micropilot FMR10
56
Hauser
"Safety settings" submenu
Navigation
Setup → Advanced setup → Safety settings
Delay time echo lost
Navigation
Setup → Advanced setup → Safety settings → Delay time echo lost
Description
Define the delay time in the case of an echo loss. After an echo loss, the device waits for
the time specified in this parameter before reacting as specified in the Diagnostic echo lost
parameter. This helps to avoid interruptions of the measurement by short-term
interferences.
User entry
0 to 600 s
Factory setting
300 s
Diagnostics echo lost
Navigation
Setup → Advanced setup → Safety settings → Diagnostics echo lost
Description
At this parameter it can be set if in case of a lost echo a warning or an alarm is issued.
Selection
• Warning
• Alarm
Factory setting
Warning