Micropilot FMR10
Operating menu
Hauser
67
13.3.2 "Simulation" submenu
Navigation
Diagnostics → Simulation
Simulation
Navigation
Diagnostics → Simulation → Simulation
Description
Select process variable to be simulated. The Simulation is used to simulate specific
measuring values or other conditions. This helps to check the correct configuration of the
device and connected control units.
Selection
• Off
• Current output
• Distance
Factory setting
Off
Value current output
Navigation
Diagnostics → Simulation → Value current output 1
Description
Defines the value of the simulated output current.
User entry
3.59 to 22.5 mA
Factory setting
3.59 mA
Process variable value
Navigation
Diagnostics → Simulation → Process variable value
Description
Value of the simulated process variable. Downstream measured value processing and the
signal output use this simulation value. In this way, users can verify whether the
measuring device has been configured correctly.
User entry
0 to 20 m
Factory setting
0 m